278
16.34 OMRON CQM1H-CPU61 [PDS]
16.34.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting Notes
PLC Type
[pds]OMRON CQM1H-
CPU61
Omron.pds
driver must be present in
\drivers
folder
Serial I/F port
RS-232, RS485 2W
Options: RS-232, RS-485 default/2W/4W – Dependant on PLC
hardware
Baud rate
9600
Options: 9600, 19200 - Must match PLC port setting
Parity
Even
Options: Odd, Even, None - Must match PLC port setting
Data bits
7
Options: 7, 8 - Must match PLC port setting
Stop bits
2
Options: 1, 2 - Must match PLC port setting
HMI station No.
0
Not used
PLC station No.
0
Options: 0-255 - As per PLC setting if not using Extended Addressing
Comm. delay (10msec) 0
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
[pds]OMRON CQM1H-CPU61 Ver1.00 supports Extended Address mode.
16.34.2 PLC Setting
Host Link Protocol Communication parameters must be the same as those of the HMI
Set Station Number as “00” if not using Extended Address mode or RS232 connections.
Compatible with:
CQM1 Series: CQM1H-CPU61, CQM1H-SCB41
CPM1H Series: SCB41
16.34.3 Wiring
16.34.3.1
Wiring for cable connections using
OMRON CQM1H-CPU61 CPU
with RS-232 Host Link D-Sub 9
Female Plug ports.
KEP Part#:
SMICOMCQM-05
(D-Sub 9 Male Socket to D-Sub 9 Male Socket Cable)
HMI PLC[RS-232]
Connect to OMRON CQM1H-CPU61 CPU RS-232 Host Link port
2 TD
Æ
3 RD
3 RD
Æ
2 TD
5 GND
Æ
9
Æ
9 GND
7 RTS
Æ
8 CTS
4 RS
Æ
5 CS
1
Æ
Shield
Æ
Earth Ground