268
16.30.3.12
Wiring for cable connections using
Watlow Anafaze PPC2000 Series Controllers
with RS232
RJ11, Female Plug ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to RJ11 Male Plug Cable)
HMI PLC[RS-232]
Connect to Watlow Electric PPC2000 Series Controllers with RS-232 Port
2 TD
Æ
2 RX
3 RD
Æ
3 TX
5 GND
Æ
1 GND
4 Shield
Æ
Earth Ground
16.30.3.13
Wiring for cable connections using
Yaskowa MP920 or MP930 Controllers
with
RS-232 D-Sub 9 pin ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to D-Sub 9 Male Socket Cable)
HMI PLC[RS-232]
Connect to Yaskowa MP920 or MP930 Controller’s
RS-232 port
2 TD
Æ
3 RD
3 RD
Æ
2 TD
5 GND
Æ
7 GND
4 RTS
Æ
5 CTS
Shield
Æ
Earth Ground
16.30.3.14
Wiring for cable connections using
Yaskawa SMC 20X0, 3010 Series Controllers
with
RS-232 D-Sub 9 pin ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to D-Sub 9 Female Plug Cable)
HMI PLC[RS-232]
Connect to Yaskawa SMC 20X0, 3010 Series Controller’s
RS-232 port
2 TD
Æ
3 RD
3 RD
Æ
2 TD
5 GND
Æ
5 GND
4 RTS
Æ
1 CTS
Shield
Æ
Earth Ground
Summary of Contents for MMI-1500