267
16.30.3.9
Wiring for cable connections using
TSX Micro and Momentum CPU’s
with RS232 RJ45 clip style
ports.
KEP Part#:
SMICMODMICRO-05
(D-Sub 9 Female Plug to RJ45 Male Plug Cable)
HMI PLC[RS-232]
Connect to TSX Micro and Momentum CPU’s with RS-232 Port
2 TD
Æ
4 SDA
3 RD
Æ
3 SDB
5 GND
Æ
9
Æ
5 GND
7 RTS
Æ
8 CTS
6 RTS
Æ
7 CTS
Shield
Æ
Earth Ground
16.30.3.10
Wiring for cable connections using
TSX Twido CPU’s
with RS232 Round 8 pin MiniDIN ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to 8 pin MiniDIN Male Plug Cable)
HMI PLC[RS-232]
Connect to TSX Twido CPU’s RS-232 Port
2 TD
Æ
4 RX
3 RD
Æ
3 TX
5 GND
Æ
7 GND
Shield
Æ
Earth Ground
16.30.3.11
Wiring for cable connections using
Watlow MLS300 Series Controllers
with RS232 RJ12 Female
Plug ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to RJ12 Male Plug Cable)
HMI PLC[RS-232]
Connect to Watlow Electric MLS300 Series Controllers with RS-232 Port
2 TD
Æ
2 RX
3 RD
Æ
6 TX
5 GND
Æ
3 GND
1 Shield
Æ
Earth Ground