HazPAC R9-8.4 User Installation Guide  

SL9258 8/2015 

 
 

 

HazPAC R9-8.4 ARM9 Touchscreen Computer 

USER INSTALLATION GUIDE 

 

 

 

ITEM#  

H95101-8R 
 

Summary of Contents for H95101-8R

Page 1: ... Sealevel Systems Inc HazPAC R9 8 4 User Installation Guide 1 SL9258 8 2015 HazPAC R9 8 4 ARM9 Touchscreen Computer USER INSTALLATION GUIDE ITEM H95101 8R ...

Page 2: ...ersonnel are permitted to install or service the equipment Do not operate the system if it has received a sharp blow been dropped or otherwise damaged in any way Contact the manufacturer for a replacement WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS AVERTISSEMENT RISQUE D EXPLOSION NE PAS DEBRANCHER TANT QUE LE CIR...

Page 3: ...gement Unit MMU MEMORY 128MB DDR2 SDRAM 256MB NAND Flash DISPLAY 8 4 400 nit TFT LCD with LED backlight 640 x 480 Resolution 16 Bit Color TOUCHSCREEN 5 wire Resistive Touchscreen with Glass Top BUS INTERFACES 10 100 BaseT Ethernet USB Device Port Two USB 2 0 Ports Dedicated RS 485 Expansion INDUSTRIAL I O Two Isolated RS 485 Ports One RS 232 Port with Full Modem Control Eight Open Collector Output...

Page 4: ...low all applicable wiring codes and regulations ENVIRONMENTAL SPECIFICATIONS Specification Operating Storage Temperature Range 30ºC to 60ºC 40ºC to 80ºC Humidity Range 10 to 90 R H Non Condensing 10 to 90 R H Non Condensing CERTIFICATIONS APPROVALS NEMA 4X IP65 protection on front panel FCC Part15 Subpart B ICES 003 Class A ETL 4000758 Conforms to ANSI UL Std 60950 1 2nd Ed CAN CSA Std C22 2 No 60...

Page 5: ...allation Guide 5 SL9258 8 2015 CLASSIFICATION This equipment is suitable only for the locations with classification specified on the product nameplate specifically Non hazardous II 3G Ex nA IIC T5 Gc Class I Div 2 Groups A B C D T5 PRODUCT MARKING ...

Page 6: ...er has been switched off or the area is known to be non hazardous Peripheral equipment must be suitable for the location in which it is used This equipment must be installed in a hazardous location classified panel rated as follows o Internal and external ambient of 30ºC to 60ºC o Minimum ingress protection rating of IP54 o ATEX IECEx Zone 2 or better o US CAN Class I Div 2 or better o Can only be...

Page 7: ...n the panel mounting plate see figures below Place the supplied 6 32 KEPS nuts on each of the twelve mounting studs Fasten only hand tight After the display is properly positioned tighten the nuts to 0 56 Nm 5 in lb of torque in the sequence pictured below Do not overtighten Repeat the sequence to ensure proper torque values are retained HazPAC R9 8 4 HazPAC R9 8 4 HazPAC R9 8 4 ...

Page 8: ...tallation to maintain hazardous location certifications USB ports require proprietary cables equipped with thumb screws supplied by Sealevel as shown in the picture below Refer to Optional Items section of the User Manual for more details When connecting power source and or RS485 terminal block ensure that the cables are routed through the cable clamp as shown in the picture below to provide a sec...

Page 9: ... Sealevel Systems Inc HazPAC R9 8 4 User Installation Guide 9 SL9258 8 2015 CAD Drawing ...

Page 10: ...e by clicking on the Drivers or Manuals links located under Technical Support Manuals and software can also be downloaded from the product page for your device The FAQ section of our website answers many common questions Refer to this helpful resource by visiting www sealevel com faq asp TECHNICAL SUPPORT Monday Friday 8 00 am to 5 00 pm EST Phone 1 864 843 4343 Email support sealevel com RETURN A...