Page 3.2 - 6
COMBIVERT R6-S
© KEB, 2008-02
Operating and appliance data
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
ru.13
Actual DC utilization
020Dh ro
-
-
0
255
1
%
-
Display of the actual utilization referring to the rated current of the regenerative unit. Only positive values
are displayed, whereby a differentiation between supply and regeneration is not possible.
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
ru.14 Actual DC peak utilization 020Eh rw
-
-
0
255
1
%
-
ru.14 enables to recognize short-term peak utilization within an operating cycle. For that the highest value
of ru.13 is stored in ru.14. The peak value memory can be cleared by pressing the UP, DOWN or ENTER
key or via bus by writing any value you like to the address of ru.14. Switching off COMBIVERT R6-S also
clears the memory.
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
ru.15
DC output current
020Fh ro
-
-
0,0
6553,5
0,1
A
-
Display of the actual DC output current in ampere.
Parameter
Addr.
R PG E Min. value Max. value Res. [?] Default
ru.16 DC output current / peak value 0210h rw
-
-
0,0
6553,5
0,1
A
-
ru.16 enables to recognize short-term peak utilization within an operating cycle. For that the highest value
of ru.15 is stored in ru.16. The peak value memory can be cleared by pressing the UP, DOWN or ENTER
key or via bus by writing any value you like to the address of ru.16. Switching off COMBIVERT R6-S also
clears the memory.
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
ru.17
AC input current
0211h
ro
-
-
-3276,7
3276,7
0,1
A
-
Display of the actual input current.
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
ru.18
DC voltage /
reference value
212h
ro
-
-
0
1000
1
V
-
The DC voltage is measured at switching on and stored as reference value. The regenerative level (cS.02)
refers proportionally to this reference value and follows to the mains voltage.
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
ru.19
DC output voltage
0213h ro
-
-
0
1000
1
V
-
Display of the actual DC output voltage. The value is measured at the DC output terminals of the
COMBIVERT R6-S.
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......