Analog outputs
© KEB, 2008-02
COMBIVERT R6-S
Page 3.3 - 3
3
10
3.3 Analog output
3.3.1 Short description analog output
The KEB COMBIVERT has one programmable analog output (ANOUT1). The variable which shall be output
at the outputs X2A.21 can be selected with An.31. ANOUT 3 and ANOUT 4 (An.41 / 47) can be output as
switching condition 42 or 43 with the digital outputs as PWM signal. The analog signal can be adapted to the
requirements with the characteristic amplifiers (
An.33...35 / 43...45 / 49...51). The ru parameters display the
actual size before and after amplification. The period for the PWM
signal can be adjusted with An.46/ 52.
Picture 7.2.1 Principle of the analog outputs
An.31/41/47
Actual line
frequency Δ
2
ru.03
Ref. DC voltage
5
ru.18
DC current
6
ru.15
AC current
7
ru.17
Digital with An.32 / 42 / 48
8
An.xx
Power module temperature
12 ru.38
Actual power
26 ru.81
An.31
An.33
An.34
An.35
X2A. 21
ANOUT1
X2A. 23
AGND
0...±100%
0...±10V
ru.3 4
ru.3 3
An.41
An.43
An.44
An.45
PWM
100%
An.46
An.47
An.49
An.50
An.51
PWM
100%
An.52
do.0...do.7
Wert “42”
do.0...do.7
Wert “43”
3.3.2 Output signals
ANOUT 1
A voltage of 0...±11,5 VDC displays the selected size in the range of 0...±115 % with a resolution of 10 bit at
the output. In order to compensate load-dependent voltage drops, the limitation at the output of the characte-
ristic amplifier is ±115 %.
Picture 7.2.2 Analog output
AGND
(X2A.23)
+
-
ANOUT1 (X2A.21) /
U
out
= 0...±11,5 V
R
B
I
max
= 5mA
R
i
< 100
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......