Seite 3.4 - 14
COMBIVERT R6-S
© KEB, 2008-02
Digital in- and outputs
do.00...do.07: Conditions
Value Function
Description
59
Inputs AND linked (ru.22)
Function
Condition met when:
AND
all selected inputs active
OR
at least one selected input active
NAND
at least one selected input inactive
NOR
all selected inputs inactive
The selection of inputs to be linked is made by the comparison level parame-
ters LE.00...LE.07.
Input ST RST F R I1
I2
I3
I4
IA
IB
IC
ID
Value
1
2
4 8 16 32 64 128 256 512 1024 2048
The sum of the inputs to query is entered in the switching levels.
Example: If condition F,R and I1 shall be linked to condition 0, value 4 + 8 +
16 = 28 must be entered in LE.00.
60
Inputs OR linked (ru.22)
61
Inputs NAND linked (ru.22)
62
Inputs NOR linked (ru.22)
63
Absolute value ANOUT1 >
level
Value of ANOUT1 (amount of ru.34 „ANOUT1 post ampl. display) higher than
the switching level.
65
ANOUT1 > level
ANOUT1 (ru.34 „ANOUT1 post ampl. display) higher than the switching le-
vel.
73
Value actual power > level
Value ru.81 „actual power“ > switching level
74
Actual power > level
ru.81 „actual power“ > switching level
80
AC input current > level
Not listed values are not assigned.
Comparison level 0...7, LE.00...LE.07
These parameters define the switching levels of the different conditions.
Switching level 0 is valid for switching condition 0, switching level 1 is valid for switching condition 1... etc.
Hysteresis 0...7, LE. 08...LE.15
The hysteresis referring to the adjusted values determine parameters LE.08...LE.15.
Hysteresis 0 (LE.08) is valid for switching level 0; LE.09 for switching level 1... etc.
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......