Page 3.2 - 18
COMBIVERT R6-S
© KEB, 2008-02
Operating and appliance data
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
SY.50 Control word low
0032h rw
-
+
0
65535
1
-
0
The control word is used for status control of the inverter via bus. The control word long (SY.43) consists of
the two 16 bit parameters control word high (SY.41) and control word low (SY.50). The status word is bit-
coded.
Bit Function
Value
Description
0
Control release
1:
ST
This bit is only effective if di.01 „select signal source“ bit 0 is
set. Then the AND operation of this bit with di.02„digital input
setting“ bit 0 is valid.
1
Automatic
2: RST
An error reset is executed when changing from not activated
(0) to activated (2).
2
Start / stop
0: Stop
Direction of rotation release or the „start “(run) command can
be given via the control word, if oP.01 „rotation source“ con-
tains the values 6, 8, 9 or 10.
4: Start
3
Clockwise /
counter clock-
wise rotation
0: Clockwise
rotation
If oP.01 „rotation source“ contains the values 8 or 9, the direc-
tion of rotation is preset via this bit.
8: Counter-clock
-
wise rotation
4...6 Parameter set
0: Set 0
Selection of the active parameter set, if in Fr.02 „parameter set
source“ the value „5: control word (
SY.50)“ is programmed.
16: Set 1
32: Set 2
48: Set 3
64: Set 4
80: Set 5
96: Set 6
112: Set 7
7
reserved
8
Fast stop on
/ off
256: Fast stop
Releases fast stop (OR operation with further fast stop sour-
ces)
9
Start approach
to reference
point
512: Start ap
-
proach to refe-
rence point
Change of not activated (0) to activated (512) starts approach
to reference point
10
Start positio-
ning
1024: Start posi
-
tioning
Change of not activated (0) to activated (1024) starts the posi-
tioning
11
Interruption
2048: Interruption
Change of not activated (0) to activated (2048) stops the po-
sitioning (drive is stopped with ramp according to positioning
profile)
12,
13
Operating
mode
0: off
Selection of the operating mode via the control word.
Only valid if in PS.00 „posi/syn
mode“ in bits 0..2 value „7: via
control word“ is programmed
4096: Synchro
-
nous running
8192: Positioning
12288: Contou
-
ring control
14,
15
reserved
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......