Operating and appliance data
© KEB, 2008-02
COMBIVERT R6-S
Page 3.2 - 9
3
10
Parameter
Addr.
R PG E Min. value
Max. value
Res. [?] Default
ru.25
Output terminal state
0219h
ro
-
-
0
255
1
-
-
Display of the external and internal
digital outputs set currently. According to following table a specific
decimal value is output for each digital output. If several outputs are set, the sum of the decimal values is
indicated.
Bit
Decimal value Output
Terminal
0
1
O1 (transistor output 1)
X2A.19
1
2
O2 (transistor output 2)
X2A.20
2
4
R1 (relay RLA,RLB,RLC)
X2A.24...26
3
8
R2 (relay FLA,FLB,FLC)
X2A.27...29
4
16
OA (internal output A)
no
5
32
OB (internal output B)
no
6
64
OC (internal output C)
no
7
128
OD (internal output D)
no
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
ru.26
Active parameter set
021Ah ro
-
-
0
7
1
-
-
The KEB COMBIVERT can have access to 8 parameter sets (0-7). Through programming the inverter can
change parameter sets autonomously and can thus start different modes of operation. This parameter
displays the actual parameter set. Independent of it another parameter set can be edited by bus (also see
chapter 3.7).
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
ru.33 ANOUT1 / pre ampl. disp. 0221h ro
-
-
-400
400
0,1
%
-
This parameter displays the value of the analog signal ANOUT1 in percent before passing the characteristic
amplifier (also see 3.3 „
Analog outputs“).
Parameter
Addr.
R PG E Min. value
Max. value Res. [?] Default
ru.34 ANOUT1 / post ampl. disp.
0222h ro
-
-
-100
100
0,1
%
-
This parameter displays the value of the signal given out at analog output ANOUT1 (terminal X2A.21) in
percent. A value of 0...±115 % corresponds to an output signal of 0...±11,5 V (also see chapt. 3.3 „Analog
outputs“).
Parameter
Addr.
R PG E Min. value Max. value Res.
[?]
Default
ru.38 Power module temperature 0226h ro
-
-
0
100
1
°C
-
ru.38 displays the actual power module temperature. On exceeding the maximum power module tempe-
rature the modulation is switched off and error E.OH is displayed. Message E.nOH is displayed after the
cooling period. The error can be reset now.
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......