Error assistance
© KEB, 2008-02
COMBIVERT R6-S
Page 5.1 - 5
5
Display COMBIVIS
Value Meaning
E.SEt
Error ! Set
39
It has been attempted to select a locked parameter set. Programmed
response “Error, restart after reset”.
E.SYn
Error! Synchronization
59
Phase allocation at commutation choke not correct.
E. UP
Error ! Undervoltage
2
Error: Undervoltage (DC-
link circuit). Occurs, if DC-link voltage falls
below the permissible value. Causes:
- input voltage too low or unstable
- Transformer capacity too small
- voltage losses through wrong cabling
Warning Messages
A.buS
Warning ! Watchdog
93
Watchdog for communication between operator / PC or operator
/ inverter has responded. The response to this warning can be
programmed.
A. EF
Warning ! ERROR external
fault
90
This warning is triggered via an external input. The response to this
warning can be programmed.
A.nOH
no ABN.STOP Power module
temperature
88
The heat sink temperature is again below the adjusted warning level.
A.nOHI no ABN.STOP Interior
temperature
92
The temperature in the interior of the inverter is again below the
warning threshold.
A.nOL
no ABN.STOP Overload
98
Warning: no more overload, OL counter has reached 0 %, warning
„overload" can be reset.
A. OH
Warning ! Power module
temperature
89
A
level can be defined, when it is exceeded this warning is
output.
Furthermore the response to this warning can be programmed.
A.OHI
Warning ! Interior
temperature
87
The temperature in the interior of the inverter lies above the permissible
level. The switch off time was started. The programmed response to
this warning message is executed.
A. OL
Warning ! Overload
99
A level between 0 and 100% of the load counter can be adjusted, when
it is exceeded this warning is output. The response to this warning can
be programmed.
A.SEt
Warning ! Set
102 It has been attempted to select a locked parameter set. The response
to this warning can be programmed.
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......