Connecting Earth Ground to QFX3600 or QFX3600-I Devices
To meet safety and electromagnetic interference (EMI) requirements and to ensure proper operation, you
must connect the QFX3600 and QFX3600-I devices to earth ground before you connect it to power.
For installations that require a separate grounding conductor to the chassis, use the protective earthing
terminal on the left rear of the chassis to connect to the earth ground (see
Before you connect earth ground to the protective earthing terminal of a QFX3600 or QFX3600-I device,
ensure that a licensed electrician has attached an appropriate grounding lug to the grounding cable.
CAUTION:
Using a grounding cable with an incorrectly attached lug can damage the
switch.
NOTE:
Mount your device in the rack or cabinet before attaching the grounding lug to the switch.
See
“Mounting a QFX3600 or QFX3600-I Device on Two Posts in a Rack or Cabinet” on page 301
and
“Mounting a QFX3600 or QFX3600-I Device on Four Posts in a Rack or Cabinet” on page 303
Ensure that you have the following parts and tools available:
•
Grounding cable for your QFX3600 or QFX3600-I device—The grounding cable must be 14 AWG (2 mm²),
minimum 90° C wire, or as permitted by the local code.
•
Grounding lug for your grounding cable—The grounding lug required is a Panduit LCD10-10A-L or
equivalent. This grounding lug is provided in the accessory kit.
•
Two M5 screws with integrated washers—The screws are used to secure the grounding lug to the
protective earthing terminal. The screws are provided in the accessory kit.
•
Phillips (+) screwdriver, number 2.
An AC-powered QFX3600 or QFX3600-I device chassis gains additional grounding when you plug the
power supply in the switch into a grounded AC power outlet by using an AC power cord appropriate for
your geographical location. See
“AC Power Cord Specifications for a QFX Series Device” on page 154
.
To connect earth ground to a QFX3600 or QFX3600-I device:
1. Connect one end of the grounding cable to a proper earth ground, such as the rack in which the device
is mounted.
2. Place the grounding lug attached to the grounding cable over the protective earthing terminal.
308
Summary of Contents for QFX3500
Page 1: ...Virtual Chassis Fabric Hardware Documentation Published 2020 11 06...
Page 225: ...Translation The emitted sound pressure is below 70 dB A per EN ISO 7779 201...
Page 229: ...205...
Page 238: ...Unterminated Fiber Optic Cable Warning 214...
Page 246: ...Restricted Access Warning 222...
Page 249: ...225...
Page 257: ...Jewelry Removal Warning 233...
Page 260: ...Operating Temperature Warning 236...
Page 271: ...DC Power Disconnection Warning 247...
Page 275: ...DC Power Wiring Sequence Warning 251...
Page 278: ...DC Power Wiring Terminations Warning 254...
Page 410: ...Figure 130 All QFX5110 VCF g050760 Figure 131 QFX5110 VCF with QFX5100 24Q Leaf Devices 386...
Page 412: ...Figure 132 QFX5100 24Q as a Leaf Device in a QFX5110 VCF 388...
Page 565: ...Table 105 System Information continued Description Field Inventory details 541...