Table 134: QFX3500 Chassis Alarm Messages (continued)
Recommended Action
CLI Message
Alarm Type
Component
For information only. Indicates the
device was powered on with two
power supplies installed, but now one
is missing. The device can continue to
operate with a single power supply. If
you wish to remove this alarm
message, reboot the device with one
power supply.
PEM pem-number Absent
Minor (yellow)
For information only. Check the power
cord connection and reconnect it if
necessary.
PEM pem-number is not powered
For information only. Indicates that an
AC power supply and DC power
supply have been installed in the same
chassis. If you wish to remove this
alarm message, reboot the device with
two AC power supplies or two DC
power supplies.
PEM pem-number Power Supply Type
Mismatch
For information only. Indicates the
device was powered on with two
power supplies installed, but one has
been removed. The device can
continue to operate with a single
power supply. If you wish to remove
this alarm message, reboot the device
with one power supply.
PEM pem-number Removed
635
Summary of Contents for QFX3500
Page 1: ...Virtual Chassis Fabric Hardware Documentation Published 2020 11 06...
Page 225: ...Translation The emitted sound pressure is below 70 dB A per EN ISO 7779 201...
Page 229: ...205...
Page 238: ...Unterminated Fiber Optic Cable Warning 214...
Page 246: ...Restricted Access Warning 222...
Page 249: ...225...
Page 257: ...Jewelry Removal Warning 233...
Page 260: ...Operating Temperature Warning 236...
Page 271: ...DC Power Disconnection Warning 247...
Page 275: ...DC Power Wiring Sequence Warning 251...
Page 278: ...DC Power Wiring Terminations Warning 254...
Page 410: ...Figure 130 All QFX5110 VCF g050760 Figure 131 QFX5110 VCF with QFX5100 24Q Leaf Devices 386...
Page 412: ...Figure 132 QFX5100 24Q as a Leaf Device in a QFX5110 VCF 388...
Page 565: ...Table 105 System Information continued Description Field Inventory details 541...