Figure 45: Clearance Requirements for Airflow and Hardware Maintenance for a QFX5110
•
For the cooling system to function properly, the airflow around the chassis must be unrestricted. See
QFX5110 Cooling System and Airflow Description for more information about the airflow through the
chassis.
•
If you are mounting a QFX5110 in a rack with other equipment, ensure that the exhaust from other
equipment does not blow into the intake vents of the chassis.
•
Leave at least 24 in. (61 cm) both in front of and behind the QFX5110. For service personnel to remove
and install hardware components, you must leave adequate space at the front and back of the switch.
NEBS GR-63 recommends that you allow at least 30 in. (76.2 cm) in front of the rack or cabinet and
24 in. (61 cm) behind the rack or cabinet.
RELATED DOCUMENTATION
QFX5110 Rack Requirements | 109
General Site Guidelines
Rack-Mounting and Cabinet-Mounting Warnings | 224
Clearance Requirements for Airflow and Hardware Maintenance for a
QFX5100 Device
When planning the site for installing a QFX5100 device, you must allow sufficient clearance around the
installed chassis (see
).
122
Summary of Contents for QFX3500
Page 1: ...Virtual Chassis Fabric Hardware Documentation Published 2020 11 06...
Page 225: ...Translation The emitted sound pressure is below 70 dB A per EN ISO 7779 201...
Page 229: ...205...
Page 238: ...Unterminated Fiber Optic Cable Warning 214...
Page 246: ...Restricted Access Warning 222...
Page 249: ...225...
Page 257: ...Jewelry Removal Warning 233...
Page 260: ...Operating Temperature Warning 236...
Page 271: ...DC Power Disconnection Warning 247...
Page 275: ...DC Power Wiring Sequence Warning 251...
Page 278: ...DC Power Wiring Terminations Warning 254...
Page 410: ...Figure 130 All QFX5110 VCF g050760 Figure 131 QFX5110 VCF with QFX5100 24Q Leaf Devices 386...
Page 412: ...Figure 132 QFX5100 24Q as a Leaf Device in a QFX5110 VCF 388...
Page 565: ...Table 105 System Information continued Description Field Inventory details 541...