10 Configuration
42
10.11 Input alarm functions
10.11.1
Alarms for analog signals and digital sensors
Open Temperature Inputs Alarm Configuration:
Device Menu > Configuration > Analog Inputs >
Temperature Inputs 1 to 2
Open Universal Inputs Alarm Configuration:
Device Menu > Configuration > Analog Inputs >
Universal Input 1 to 3 > Configuration
Open pH/Redox/NH
3
Analysis Inputs Alarm Configuration:
Device Menu > Configuration > Analog Inputs >
Analysis Input 1 to 4 > Configuration
Open CR / Ci Analysis Inputs Alarm Configuration:
Device Menu > Configuration > Analog Inputs >
Analysis Input 1 to 4 > Configuration > Measuring Range 1 to 4
Open Alarm Configuration Inputs for Digital Sensors:
Device Menu > Configuration > Digital Sensors >
Digital Sensors 1 to 6 > Configuration
Open Alarm Configuration For External Analog Inputs:
Device Menu > Configuration > External Analog Inputs >
External Analog inputs 1 to 8
Open Alarm Configuration For Flow Rate:
Device Menu > Configuration > Flow Rate > Flow Rate 1 to 2
Configuration point Selection/
setting option
Explanation
Digital signal for hold Selection from the
binary selector
Digital signal for activating the hold function
When the hold function is activated, the alarm as-
sumes the state defined in the "Response at
hold" setting.
Response at hold
inactive
active
hold
Specification of the alarm state when the hold
function is activated, at calibration of the particu-
lar input or at error (out of range)
inactive:
alarm suppressed
active:
alarm forced
hold:
alarm state is maintained regardless of
alarm condition changes
normal:
alarm in acc. with alarm condition
Response at
calibration
inactive
active
hold
normal
Response at error
inactive
active
hold
Summary of Contents for AQUIS touch S
Page 8: ...Inhalt ...
Page 20: ...10 Configuration 20 Chapter 10 12 Calibration timer page 46 ...
Page 68: ...13 Calibrating redox sensors 68 ...
Page 78: ...15 Calibrating CR conductivity sensors 78 ...
Page 88: ...16 Calibrating Ci conductivity sensors 88 ...
Page 96: ...17 Calibrating universal inputs 96 ...
Page 106: ...18 Calibrating O DO sensors 106 ...
Page 146: ...21 Annex 146 ...
Page 147: ......
Page 148: ......
Page 149: ......