21 Annex
138
21.2.2
Voltage supply to the bus with DC 5 V from a JUMO digiLine hub
The line length specifications in this subchapter apply when supplying JUMO
ecoLine sensors and sensors with JUMO digiLine electronics with DC 5 V from
a JUMO digiLine hub. In this case, the JUMO digiLine hub must be supplied with
DC 24 V. The slide switch on the JUMO digiLine hub must be set to the position
for DC 24 V as the input voltage. The electronics of the JUMO digiLine hub gen-
erate the bus supply voltage of DC 5 V internally and supply its outputs with this
voltage.
Bus cabling in line topology
In the line topology, the bus line must be provided with terminating resistors at
both ends wherever possible, in order to avoid transmission interference
through reflections. If JUMO ecoLine sensors are used, however, terminating re-
sistors must not be employed. You should therefore use terminating resistors
only in a JUMO digiLine bus without JUMO ecoLine sensors. M12 terminating
connectors are available from JUMO for the bus termination.
⇨
Chapter 4.4 "Accessories", page 21
Terminating resistors can be activated via DIP switch on the options board for
serial interface RS422/485.
⇨
Chapter "Optional board interfaces", page 64
Sensor type
Max. length of
bus line
a
Max. length of
stub lines
b
Max. number of con-
nectable sensors
Comment
JUMO digiLine pH/
ORP/T
200 m
10 m
6
-
JUMO ecoLine O-DO
JUMO ecoLine NTU
200 m
10 m
6
Bus termination
is not permissi-
ble
a
The maximum length of the bus line depends on the number and type of connected sensors and on how
they are distributed along the bus line. Due to the widely varying current consumptions of the different
sensor types, it is difficult to state a generate value that will apply for all installation situations. In case of
doubt, it is advisable to carry out a voltage drop calculation during the planning phase (cf. Chapter 21.2.4
"Voltage drop calculation", page 142).
b
Stub line from a JUMO digiLine hub or Y-distributor up to a sensor with JUMO digiLine electronics
Summary of Contents for AQUIS touch S
Page 8: ...Inhalt ...
Page 20: ...10 Configuration 20 Chapter 10 12 Calibration timer page 46 ...
Page 68: ...13 Calibrating redox sensors 68 ...
Page 78: ...15 Calibrating CR conductivity sensors 78 ...
Page 88: ...16 Calibrating Ci conductivity sensors 88 ...
Page 96: ...17 Calibrating universal inputs 96 ...
Page 106: ...18 Calibrating O DO sensors 106 ...
Page 146: ...21 Annex 146 ...
Page 147: ......
Page 148: ......
Page 149: ......