Table 13: ZY04 to 12 High Static Indoor Blower - Without Powered Convenience Outlet
Compressor 1
Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating
/ Pwr Exh
Si
ze
(T
on
s)
N
om
in
al
U
ni
t V
ol
ta
ge
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA
(Amps)
2, 3
Min Fuse
/ Breaker
Size (Amps)
Max Fuse
/ Breaker
Size (Amps)
FLA LRA
MCA
w/Pwr Exh (Amps)
Min Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
Max Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
FLA LRA
None
-
-
-
45.6
50
50
49 249
47.8
50
60
51 259
11725 12
1
33.3
54.4
60
60
50 249
57.1
60
60
53 259
12525 18.6
1
51.6
77.3
80
80
71 249
80
90
90
74 259
13225 24
1
66.6
96
100
100
88 249
98.8
100 100 91 259
208-3-60 13.7 83.1 21 13.7 83.1 21
2.3
10.2
1.1
14225 31.8
2
88.3
123.1
125
125
113 249
125.9
150 150 116 259
None
-
-
-
45.6
50
50
49 255
47.6
50
60
51 250
11725 16
1
38.5
60.9
70
70
56 255
63.4
70
70
58 250
12525 24.8
1
59.7
87.4
90
90
80 255
89.9
90
90
83 250
13225 32
1
77
109
110
110
100 255
111.5
125 125 103 250
230-3-60 13.7 83.1 21 13.7 83.1 21
2.3
10.2
1
14225 42.4
2
102
140.3
150
150
129 255
142.8
150 150 131 250
None
-
-
-
21.4
25
25
23 128
22.4
25
25
24 125
11746 16.5
1
19.8
30.8
35
35
28 128
32
35
35
29 125
12846 27.8
1
33.4
47.8
50
50
44 128
49
50
50
45 125
13346 33
1
39.7
55.6
60
60
51 128
56.9
60
60
52 125
460-3-60 6.2 41
10
6.2 41
10
1.3
4.8
0.5
14246 41.7
2
50.2
68.8
70
70
63 128
70
70
70
64 125
None
-
-
-
16.4
20
20
17 103
17.2
20
20
18 100
11758 17
1
16.4
24.8
25
25
23 103
25.8
30
30
24 100
09 (8.5)
575-3-60 4.8 33
8
4.8 33
8
1.1
3.4
0.4
13458 34
1
32.7
45.1
50
50
42 103
46.1
50
50
42 100
None
-
-
-
56.7
60
70
61 323
58.9
60
70
63 333
11725 12
1
33.3
60.3
70
70
61 323
63
70
70
63 333
12525 18.6
1
51.6
83.1
90
90
76 323
85.9
90
90
79 333
13225 24
1
66.6
101.9
110
110
94 323
104.6
110 110 96 333
208-3-60 16 110 25
16 110
25
5.8
14.9
1.1
14225 31.8
2
88.3
129
150
150
119 323
131.8
150 150 121 333
None
-
-
-
56.2
60
70
60 322
58.2
60
70
62 327
11725 16
1
38.5
66.9
70
70
62 322
69.4
70
70
64 327
12525 24.8
1
59.7
93.4
100
100
86 322
95.9
100 100 88 327
13225 32
1
77
115
125
125
106 322
117.5
125 125 108 327
230-3-60 16 110 25
16 110
25
5.2
15
1
14225 42.4
2
102
146.3
150
150
135 322
148.8
150 150 137 327
None
-
-
-
28
30
35
30 159
29
30
35
31 161
11746 16.5
1
19.8
34.1
35
35
31 159
35.4
40
40
33 161
12846 27.8
1
33.4
51.1
60
60
47 159
52.4
60
60
48 161
13346 33
1
39.7
59
60
60
54 159
60.3
70
70
55 161
460-3-60 7.8 52
12
7.8 52
12
2.9
7.5
0.5
14246 41.7
2
50.2
72.1
80
80
66 159
73.4
80
80
68 161
None
-
-
-
20.6
25
25
22 124
21.4
25
25
23 126
11758 17
1
16.4
27.5
30
30
25 124
28.5
30
30
26 126
12 (10)
575-3-60 5.7 38.9
9
5.7 38.9
9
2.2
5.6
0.4
13458 34
1
32.7
47.9
50
50
44 124
48.9
50
50
45 126
1
Minimum Circuit Ampacity.
2
Dual Element, Time Delay Type.
3
HACR type per NEC.
4
Non-fused Disconnect. Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field
installed electric heat kits may exceed the factory installed disconnect amperage rating.
INSTALLATION MANUAL ZY SERIES 3 - 10 ton 60 Hertz R-410A
55
Johnson Controls Ducted Systems
Summary of Contents for ZY Series
Page 2: ...2 INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 140: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 140 Johnson Controls Ducted Systems ...
Page 141: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 141 Johnson Controls Ducted Systems ...
Page 142: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 142 Johnson Controls Ducted Systems ...
Page 143: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 143 Johnson Controls Ducted Systems ...