![Johnson Controls ZY Series Installation Manual Download Page 133](http://html.mh-extra.com/html/johnson-controls/zy-series/zy-series_installation-manual_2023251133.webp)
Table 82: ZY06 Charging Table
Air Flow Indoor Db/Wb
Outdoor DB
Suction P
Suction Temp.
Liquid P
Liquid Temp.
Delta T Db
Compr. amps
75
139
65
280
83
-25
13.1
85
138
63
329
92
-26
14.9
300 Cfm/Ton 80/62
95
136
62
378
101
-27
16.8
75
140
64
285
83
-25
13.2
85
141
65
334
92
-25
15.1
300 Cfm/Ton 80/67
95
143
66
384
100
-24
17.0
75
140
64
290
84
-25
13.3
85
145
66
340
91
-23
15.3
300 Cfm/Ton 80/72
95
150
69
390
99
-20
17.2
75
133
61
276
82
-23
12.9
85
134
61
327
91
-23
14.9
300 Cfm/Ton 75/62
95
134
61
379
100
-23
16.8
75
144
67
282
82
-23
13.1
85
145
66
331
92
-23
15.0
400 Cfm/Ton 80/62
95
146
66
381
102
-23
16.9
75
145
67
286
83
-22
13.3
85
147
66
331
91
-22
15.0
400 Cfm/Ton 80/67
95
149
66
377
100
-21
16.7
75
146
66
289
83
-22
13.4
85
149
67
331
91
-21
14.9
400 Cfm/Ton 80/72
95
152
67
373
98
-20
16.5
75
138
63
279
81
-20
13.0
85
140
63
329
91
-20
14.9
400 Cfm/Ton 75/62
95
142
64
380
100
-19
16.8
Table 83: ZY07 Charging Table
Air Flow Indoor Db/Wb
Outdoor DB
Suction P
Suction Temp.
Liquid P
Liquid Temp.
Delta T Db
Compr. amps
75
135
60
269
75
-26
17.7
85
135
59
317
85
-26
19.7
300 Cfm/Ton 80/62
95
135
58
365
95
-26
21.6
75
134
58
268
75
-26
17.8
85
138
59
318
85
-25
19.7
300 Cfm/Ton 80/67
95
141
61
368
95
-24
21.7
75
134
57
267
75
-27
17.8
85
140
60
319
85
-24
19.8
300 Cfm/Ton 80/72
95
146
63
371
95
-21
21.8
75
129
56
268
75
-24
17.6
85
131
56
317
85
-23
19.6
300 Cfm/Ton 75/62
95
132
56
365
95
-23
21.6
75
139
62
270
75
-23
17.8
85
141
62
318
85
-23
19.8
400 Cfm/Ton 80/62
95
143
61
366
95
-23
21.7
75
140
62
269
75
-23
17.9
85
143
62
319
85
-22
19.8
400 Cfm/Ton 80/67
95
146
62
368
95
-21
21.8
75
141
61
268
75
-23
17.9
85
145
62
319
85
-21
19.9
400 Cfm/Ton 80/72
95
150
63
371
95
-19
21.9
75
134
58
270
75
-21
17.7
85
136
59
318
85
-20
19.7
400 Cfm/Ton 75/62
95
138
59
367
95
-19
21.7
INSTALLATION MANUAL ZY SERIES 3 - 10 ton 60 Hertz R-410A
133
Johnson Controls Ducted Systems
Summary of Contents for ZY Series
Page 2: ...2 INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 140: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 140 Johnson Controls Ducted Systems ...
Page 141: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 141 Johnson Controls Ducted Systems ...
Page 142: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 142 Johnson Controls Ducted Systems ...
Page 143: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 143 Johnson Controls Ducted Systems ...