Table 10: ZY04 to 12 Standard Static Indoor Blower - With Powered Convenience Outlet
Compressor 1
Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating
/ Pwr Exh
Si
ze
(T
on
s)
N
om
in
al
U
ni
t V
ol
ta
ge
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA
(Amps)
2, 3
Min Fuse
/ Breaker
Size (Amps)
Max Fuse
/ Breaker
Size (Amps)
FLA LRA
MCA
w/Pwr Exh (Amps)
Min Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
Max Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
FLA LRA
None
-
-
-
53.1
60
60
56 306
55.3
60
70
59 316
11725 12
1
33.3
55.8
60
60
56 306
58.5
60
70
59 316
12525 18.6
1
51.6
78.6
80
80
72 306
81.4
90
90
75 316
13225 24
1
66.6
97.4
100
100
90 306
100.1
110 110 92 316
208-3-60 16 110 25
16 110
25
5.8
7
1.1
8.6
14225 31.8
2
88.3
124.5
125
125
115 306
127.3
150 150 117 316
None
-
-
-
52.7
60
60
56 305
54.7
60
70
58 310
11725 16
1
38.5
62.5
70
70
58 305
65
70
70
60 310
12525 24.8
1
59.7
89
90
90
82 305
91.5
100 100 84 310
13225 32
1
77
110.6
125
125
102 305
113.1
125 125 104 310
230-3-60 16 110 25
16 110
25
5.2
7.2
1
8.6
14225 42.4
2
102
141.9
150
150
131 305
144.4
150 150 133 310
None
-
-
-
26.3
30
30
28 148
27.3
30
30
29 150
11746 16.5
1
19.8
31.9
35
35
29 148
33.2
35
35
31 150
12846 27.8
1
33.4
48.9
50
50
45 148
50.2
60
60
46 150
13346 33
1
39.7
56.8
60
60
52 148
58.1
60
60
53 150
460-3-60 7.8 52
12
7.8 52
12
2.9
3.6
0.5
8.6
14246 41.7
2
50.2
69.9
70
70
64 148
71.2
80
80
65 150
None
-
-
-
19.2
20
20
20 109
20
20
20
21 110
11758 17
1
16.4
25.8
30
30
24 109
26.8
30
30
25 110
12 (10)
575-3-60 5.7 38.9
9
5.7 38.9
9
2.2
2.5
0.4
8.6
13458 34
1
32.7
46.2
50
50
42 109
47.2
50
50
43 110
1
Minimum Circuit Ampacity.
2
Dual Element, Time Delay Type.
3
HACR type per NEC.
4
Non-fused Disconnect. Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field
installed electric heat kits may exceed the factory installed disconnect amperage rating.
INSTALLATION MANUAL ZY SERIES 3 - 10 ton 60 Hertz R-410A
40
Johnson Controls Ducted Systems
Summary of Contents for ZY Series
Page 2: ...2 INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 140: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 140 Johnson Controls Ducted Systems ...
Page 141: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 141 Johnson Controls Ducted Systems ...
Page 142: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 142 Johnson Controls Ducted Systems ...
Page 143: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 143 Johnson Controls Ducted Systems ...