![Johnson Controls ZY Series Installation Manual Download Page 136](http://html.mh-extra.com/html/johnson-controls/zy-series/zy-series_installation-manual_2023251136.webp)
Table 88: ZY09 Charging Table System 2
Air Flow Indoor Db/Wb
Outdoor DB
Suction P
Suction Temp.
Liquid P
Liquid Temp.
Delta T Db
Compr. amps
75
137
64
278
78
-26
7.2
85
137
62
323
88
-27
8.1
300 Cfm/Ton 80/62
95
137
59
369
98
-27
8.9
75
137
62
275
78
-26
7.2
85
140
62
324
88
-25
8.1
300 Cfm/Ton 80/67
95
143
62
374
99
-24
9.0
75
137
60
272
78
-27
7.1
85
143
62
325
89
-24
8.1
300 Cfm/Ton 80/72
95
149
64
378
99
-21
9.1
75
132
60
276
78
-24
7.2
85
133
59
322
88
-23
8.1
300 Cfm/Ton 75/62
95
135
58
369
98
-23
8.9
75
141
67
280
78
-23
7.3
85
143
65
326
89
-23
8.1
400 Cfm/Ton 80/62
95
146
63
372
99
-23
9.0
75
142
66
279
78
-23
7.2
85
146
65
327
89
-22
8.1
400 Cfm/Ton 80/67
95
149
64
376
99
-21
9.0
75
144
65
277
78
-23
7.2
85
148
65
328
89
-21
8.1
400 Cfm/Ton 80/72
95
152
65
379
99
-20
9.1
75
136
63
278
78
-21
7.3
85
139
62
325
88
-20
8.1
400 Cfm/Ton 75/62
95
142
61
373
98
-20
9.0
Table 89: ZY12 Charging Table System 1
Air Flow Indoor Db/Wb
Outdoor DB
Suction P
Suction Temp.
Liquid P
Liquid Temp.
Delta T Db
Compr. amps
75
135
59
284
81
-26
8.9
85
135
58
332
90
-26
10.0
300 Cfm/Ton 80/62
95
135
58
380
98
-27
11.0
75
134
59
285
81
-26
9.1
85
138
59
334
91
-25
10.1
300 Cfm/Ton 80/67
95
142
60
383
100
-24
11.0
75
132
58
285
81
-26
9.3
85
141
60
336
91
-23
10.1
300 Cfm/Ton 80/72
95
149
62
387
101
-20
11.0
75
129
56
282
80
-23
8.9
85
131
56
330
89
-23
10.0
300 Cfm/Ton 75/62
95
133
56
379
98
-23
11.0
75
139
61
285
83
-23
9.0
85
142
61
333
91
-23
10.0
400 Cfm/Ton 80/62
95
144
61
382
100
-23
11.0
75
140
61
287
82
-22
9.1
85
144
62
336
91
-22
10.1
400 Cfm/Ton 80/67
95
148
62
385
100
-21
11.1
75
140
61
289
82
-22
9.2
85
146
62
338
91
-20
10.2
400 Cfm/Ton 80/72
95
151
63
388
100
-19
11.1
75
134
58
284
81
-20
9.0
85
137
58
332
90
-20
10.0
400 Cfm/Ton 75/62
95
140
59
381
99
-19
11.0
INSTALLATION MANUAL ZY SERIES 3 - 10 ton 60 Hertz R-410A
136
Johnson Controls Ducted Systems
Summary of Contents for ZY Series
Page 2: ...2 INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 140: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 140 Johnson Controls Ducted Systems ...
Page 141: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 141 Johnson Controls Ducted Systems ...
Page 142: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 142 Johnson Controls Ducted Systems ...
Page 143: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 143 Johnson Controls Ducted Systems ...