ZY04 to 12 Side Duct Application (Belt Drive)
Table 32: ZY04 (3.0 Ton) Side Duct
1
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
900
n/a
n/a
874
0.31
972
0.40
1065
0.50
1153
0.60
1236
0.70
1315
0.80
1390
0.89
1460
0.97
1526
1.05
1000
n/a
n/a
887
0.36
985
0.45
1078
0.55
1165
0.65
1249
0.75
1328
0.85
1402
0.94
1472
1.03
1539
1.10
1100
797
0.33
900
0.42
998
0.51
1091
0.61
1179
0.71
1263
0.81
1341
0.91
1416
1.00
1486
1.08
1553
1.16
1200
813
0.40
916
0.48
1014
0.57
1107
0.67
1195
0.77
1279
0.87
1357
0.97
1432
1.06
1502
1.15
1569
1.22
1300
831
0.46
935
0.55
1033
0.64
1126
0.74
1214
0.84
1297
0.94
1376
1.03
1450
1.13
1520
1.21
1583
1.28
1400
852
0.53
956
0.61
1054
0.71
1146
0.80
1234
0.90
1318
1.00
1396
1.10
1471
1.19
1541
1.28
--
--
1500
876
0.59
979
0.68
1077
0.77
1170
0.87
1258
0.97
1341
1.07
1420
1.17
1494
1.26
1565
1.34
--
--
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.9-hp
--
Exceeds recommended blower speed
1
Blower performance includes gas heat exchangers and 2 in. filters. See STATIC RESISTANCE table for additional applications.
Note:
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. kW = 0.929
x BHP
Table 33: ZY05 (4.0 Ton) Side Duct
1
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1200
840
0.30
927
0.41
1012
0.53
1096
0.65
1177
0.77
1257
0.89
1334
1.01
1411
1.12
1485
1.22
1558
1.31
1300
857
0.35
944
0.47
1029
0.59
1112
0.71
1194
0.83
1273
0.95
1351
1.07
1427
1.18
1502
1.28
1574
1.37
1400
875
0.42
962
0.53
1048
0.65
1131
0.77
1212
0.89
1292
1.01
1370
1.13
1446
1.24
1520
1.34
1593
1.43
1500
897
0.49
984
0.60
1069
0.72
1152
0.84
1233
0.96
1313
1.08
1391
1.20
1467
1.31
1542
1.41
--
--
1600
921
0.56
1008
0.67
1093
0.79
1176
0.91
1258
1.04
1337
1.16
1415
1.27
1491
1.38
1566
1.49
--
--
1700
948
0.64
1035
0.76
1120
0.87
1204
1.00
1285
1.12
1365
1.24
1442
1.36
1518
1.47
1593
1.57
--
--
1800
979
0.73
1066
0.85
1151
0.96
1234
1.08
1315
1.21
1395
1.33
1473
1.44
1549
1.56
--
--
--
--
1900
1012
0.83
1099
0.94
1185
1.06
1268
1.18
1349
1.30
1429
1.42
1507
1.54
1583
1.65
--
--
--
--
2000
1049
0.93
1136
1.04
1222
1.16
1305
1.28
1386
1.40
1466
1.52
1544
1.64
--
--
--
--
--
--
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.9-hp
--
Exceeds recommended blower speed
1
Blower performance includes gas heat exchangers and 2 in. filters. See STATIC RESISTANCE table for additional applications.
Note:
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. kW = 0.929
x BHP
INSTALLATION MANUAL ZY SERIES 3 - 10 ton 60 Hertz R-410A
86
Johnson Controls Ducted Systems
Summary of Contents for ZY Series
Page 2: ...2 INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 140: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 140 Johnson Controls Ducted Systems ...
Page 141: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 141 Johnson Controls Ducted Systems ...
Page 142: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 142 Johnson Controls Ducted Systems ...
Page 143: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 143 Johnson Controls Ducted Systems ...