Table 24: ZY12 Physical Data
Model
Component
ZYG12
ZYE12
Nominal Tonnage
10
10
Airflow Option
A
B
C
A
B
C
Quantity
1
1
1
1
1
1
Fan Size (in.)
15 x 15
15 x 15
15 x 15
15 x 15
15 x 15
15 x 15
Type
Centrifugal
Centrifugal
Motor Sheave
1VL44
1VP50
1VP56
1VL44
1VP50
1VP56
Blower Sheave
AK79
AK79
BK85
AK79
AK79
BK85
Belt
A50
A50
BX52
A50
A50
BX52
Motor Max Bhp, 3 Phase
2.4
3.7
5.25
2.4
3.7
5.25
RPM
1725
1725
1725
1725
1725
1725
EVAP FAN DATA BELT DRIVE
Frame size
56Y
56HZ
145TY
56Y
56HZ
145TY
FILTERS
Quantity - Size
1
4 - (20 x 20 x 2)
4 - (20 x 20 x 2)
1
2 in. Throwaway, Standard, MERV 4 (Minimum Efficiency Reporting Value).
Optional Gas Heat
These gas-fired heaters have aluminized-steel or
optional stainless steel, tubular heat exchangers
with spark ignition.
Gas piping
Proper sizing of gas piping depends on the cubic
feet per hour of gas flow required, specific gravity
of the gas and the length of run. "National Fuel
Gas Code" Z223.1 (in U.S.A.) or the current Gas
Installation Codes CSA-B149.1 (in Canada) should
be followed in all cases unless superseded by local
codes or gas utility requirements. Refer to Table
25. The heating value of the gas may differ with
locality. The value should be checked with the local
gas utility.
Figure 24: Side Entry Gas Piping
Note:
Routing of gas piping must not interfere
with the flue or heat compartment access.
Table 25: Gas Pipe Sizing - Capacity of Pipe
Nominal Iron Pipe Size
Length of
Pipe (ft)
3/4 in.
1 in.
1-1/4 in.
10
278
520
1050
20
190
350
730
30
152
285
590
40
130
245
500
50
115
215
440
60
105
195
400
70
96
180
370
80
90
170
350
90
84
160
320
100
79
150
305
Note:
Maximum capacity of pipe in cubic feet
of gas per hour based upon a pressure drop of
0.3 inch W.C. and 0.6 specific gravity gas.
Note:
There may be a local gas utility
requirement specifying a minimum diameter
for gas piping. Units require either a 1/2 or 3/4
inch pipe connection at the entrance fitting.
Line should not be sized smaller than the
entrance fitting size.
INSTALLATION MANUAL ZY SERIES 3 - 10 ton 60 Hertz R-410A
78
Johnson Controls Ducted Systems
Summary of Contents for ZY Series
Page 2: ...2 INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 140: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 140 Johnson Controls Ducted Systems ...
Page 141: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 141 Johnson Controls Ducted Systems ...
Page 142: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 142 Johnson Controls Ducted Systems ...
Page 143: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 143 Johnson Controls Ducted Systems ...