ZY04-12 unit weights
Figure 8: Unit 4 Point Load Weight
Figure 9: Unit 6 Point Load Weight
Figure 10: Center of Gravity
Table 2: ZY04-12 Corner Weights
Weight (lb)
Center of Gravity
4 Point Load Location (lb)
6 Point Load Location (lb)
Model
Size
(Tons)
Shipping
Operating
X
Y
A
B
C
D
A
B
C
D
E
F
ZYE
04 (3)
486
481
36
25
127
118
113
122
86
82
78
75
78
82
ZYE
05 (4)
569
564
36
25
145
140
137
142
97
95
93
91
93
95
ZYE
06 (5)
587
582
36
25
151
145
140
146
101
99
96
93
95
98
ZYE
07 (6)
730
725
44
36
206
211
156
153
137
139
141
104
103
101
ZYE
A7 (6)
849
829
45.0
35.3
229
244
183
172
151
158
165
124
118
113
ZYE
08 (7.5)
873
868
46
36
236
268
193
171
154
167
182
132
121
111
ZYE
09 (8.5)
878
878
46
36
241
265
195
177
158
168
180
132
124
116
ZYE
12 (10)
907
902
47
36
239
278
207
178
155
171
190
142
128
116
ZYG
04 (3)
532
527
36
27
147
136
117
126
99
94
90
77
81
85
ZYG
05 (4)
623
618
36
26
167
156
142
152
113
108
103
94
98
103
ZYG
06 (5)
641
636
35
26
174
159
144
159
118
111
104
95
101
108
ZYG
07 (6)
800
795
43
37
237
233
161
164
159
157
155
107
108
109
ZYG
A7 (6)
919
899
45.0
35.3
249
265
199
187
164
171
179
134
128
123
ZYG
08 (7.5)
975
970
44
37
287
294
197
193
191
193
196
132
130
128
ZYG
09 (8.5)
980
980
45
36
279
292
209
200
184
190
196
141
136
132
ZYG
12 (10)
1013
1008
45
36
285
300
217
206
189
195
202
146
141
136
INSTALLATION MANUAL ZY SERIES 3 - 10 ton 60 Hertz R-410A
14
Johnson Controls Ducted Systems
Summary of Contents for ZY Series
Page 2: ...2 INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 140: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 140 Johnson Controls Ducted Systems ...
Page 141: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 141 Johnson Controls Ducted Systems ...
Page 142: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 142 Johnson Controls Ducted Systems ...
Page 143: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 143 Johnson Controls Ducted Systems ...