Table 86: ZY08 Charging Table System 2
Air Flow Indoor Db/Wb
Outdoor DB
Suction P
Suction Temp.
Liquid P
Liquid Temp.
Delta T Db
Compr. amps
75
140
59
264
81
-25
6.9
85
140
58
316
89
-26
7.9
300 Cfm/Ton 80/62
95
139
56
368
97
-27
8.9
75
141
59
264
81
-25
6.9
85
145
59
314
90
-24
7.8
300 Cfm/Ton 80/67
95
148
59
364
100
-23
8.8
75
142
58
264
81
-25
6.9
85
150
60
312
92
-23
7.8
300 Cfm/Ton 80/72
95
157
61
361
102
-20
8.6
75
134
56
265
79
-23
6.9
85
135
56
317
88
-23
7.9
300 Cfm/Ton 75/62
95
137
55
369
97
-23
8.9
75
144
61
265
81
-23
6.9
85
147
61
316
90
-23
7.9
400 Cfm/Ton 80/62
95
149
60
367
99
-23
8.8
75
147
62
264
82
-23
6.9
85
150
61
314
92
-22
7.8
400 Cfm/Ton 80/67
95
153
60
365
101
-21
8.8
75
149
62
263
84
-22
6.9
85
153
61
312
93
-21
7.8
400 Cfm/Ton 80/72
95
158
61
362
102
-19
8.7
75
139
58
265
80
-21
6.9
85
142
58
317
89
-20
7.9
400 Cfm/Ton 75/62
95
144
58
369
98
-19
8.9
Table 87: ZY09 Charging Table System 1
Air Flow Indoor Db/Wb
Outdoor DB
Suction P
Suction Temp.
Liquid P
Liquid Temp.
Delta T Db
Compr. amps
75
138
63
278
79
-26
7.7
85
138
61
325
89
-27
8.5
300 Cfm/Ton 80/62
95
137
59
371
98
-27
9.3
75
137
62
277
80
-26
7.6
85
141
62
325
89
-25
8.5
300 Cfm/Ton 80/67
95
144
62
374
98
-24
9.3
75
137
61
275
80
-27
7.6
85
144
63
325
90
-24
8.5
300 Cfm/Ton 80/72
95
151
64
376
99
-21
9.3
75
132
60
277
78
-24
7.6
85
133
58
325
88
-23
8.5
300 Cfm/Ton 75/62
95
134
57
372
97
-23
9.4
75
142
66
281
79
-23
7.7
85
144
64
327
89
-23
8.5
400 Cfm/Ton 80/62
95
146
63
374
99
-23
9.4
75
143
65
279
80
-23
7.7
85
147
64
327
90
-22
8.5
400 Cfm/Ton 80/67
95
150
64
375
99
-21
9.4
75
144
64
278
81
-23
7.7
85
149
64
327
90
-21
8.5
400 Cfm/Ton 80/72
95
155
65
376
99
-20
9.3
75
137
62
280
79
-21
7.7
85
139
61
327
88
-20
8.5
400 Cfm/Ton 75/62
95
141
61
375
98
-20
9.4
INSTALLATION MANUAL ZY SERIES 3 - 10 ton 60 Hertz R-410A
135
Johnson Controls Ducted Systems
Summary of Contents for ZY Series
Page 2: ...2 INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 140: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 140 Johnson Controls Ducted Systems ...
Page 141: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 141 Johnson Controls Ducted Systems ...
Page 142: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 142 Johnson Controls Ducted Systems ...
Page 143: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 143 Johnson Controls Ducted Systems ...