Table 75: Smart Equipment™ Economizer Board Details
Board Label
Cover Label
Description
Function and Comments
IN8
BLDG PRES 0-5 VDC positive input from the Building Pressure sensor
BldgPres parameter reports input status (-.250-.250”/w/-.062-.062kPa). Used
for modulating power exhaust functions when ExFType selection is Modulating
Damper or Variable Frequency Fan.
C
COM
24 VAC common/0-5 VDC negative for the building
pressure sensor
Connects through circuit trace to 24V~ IN pin COM
BINARY INPUTS at right on lower edge of economizer board
PURGE
24 VAC hot input from the PURGE dry contact
Purge parameter reports input status (False with 0 VAC input-True with 24 VAC
input). When Purge status is True, heating and cooling operation is prevented,
the indoor blower and power exhaust fan operate, the economizer actuator is
positioned to 100%.
IN9
24V~
24 VAC hot supplied for the purge dry contact
Connects through circuit trace to 24V~ IN pin HOT
EX VFD FLT
24 VAC hot input from the power Exhaust Variable
Frequency Drive Fault contact
ExFanVFDFlt parameter reports input status (Normal with 0 VAC input-Alarm
with 24 VAC input) when ExFType selection is Variable Frequency Fan. When
ExFanVFDFlt status is Alarm, EX-FAN fan output is prevented.
IN10
24V~
24 VAC hot supplied for the power exhaust variable
frequency drive fault contact
Connects through circuit trace to 24V~ IN pin HOT
1
When wiring unit and other devices using the SA Bus and FC Bus, see Table "Cable for FC Buses and SA Buses in Order of
Preference".
INSTALLATION MANUAL ZY SERIES 3 - 10 ton 60 Hertz R-410A
117
Johnson Controls Ducted Systems
Summary of Contents for ZY Series
Page 2: ...2 INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 140: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 140 Johnson Controls Ducted Systems ...
Page 141: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 141 Johnson Controls Ducted Systems ...
Page 142: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 142 Johnson Controls Ducted Systems ...
Page 143: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 143 Johnson Controls Ducted Systems ...