Table 90: ZY12 Charging Table System 2
Air Flow Indoor Db/Wb
Outdoor DB
Suction P
Suction Temp.
Liquid P
Liquid Temp.
Delta T Db
Compr. amps
75
134
60
279
79
-26
8.4
85
135
59
327
88
-26
9.4
300 Cfm/Ton 80/62
95
135
59
376
98
-27
10.3
75
135
60
279
79
-26
8.6
85
139
60
330
89
-25
9.5
300 Cfm/Ton 80/67
95
142
60
381
99
-24
10.4
75
136
60
280
79
-26
8.8
85
143
61
332
89
-23
9.6
300 Cfm/Ton 80/72
95
150
62
385
99
-20
10.5
75
128
57
278
78
-23
8.4
85
130
57
328
88
-23
9.4
300 Cfm/Ton 75/62
95
132
57
377
98
-23
10.4
75
139
62
278
80
-23
8.4
85
141
62
328
89
-23
9.3
400 Cfm/Ton 80/62
95
143
61
378
99
-23
10.2
75
141
62
280
79
-22
8.6
85
144
62
331
89
-22
9.5
400 Cfm/Ton 80/67
95
147
63
381
98
-21
10.4
75
142
62
282
78
-22
8.7
85
147
63
333
88
-20
9.6
400 Cfm/Ton 80/72
95
152
64
385
98
-19
10.5
75
134
59
278
79
-20
8.4
85
137
59
328
88
-20
9.3
400 Cfm/Ton 75/62
95
139
59
378
98
-19
10.3
INSTALLATION MANUAL ZY SERIES 3 - 10 ton 60 Hertz R-410A
137
Johnson Controls Ducted Systems
Summary of Contents for ZY Series
Page 2: ...2 INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 140: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 140 Johnson Controls Ducted Systems ...
Page 141: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 141 Johnson Controls Ducted Systems ...
Page 142: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 142 Johnson Controls Ducted Systems ...
Page 143: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 143 Johnson Controls Ducted Systems ...