Table 16: ZY04 to 12 High Static Indoor Blower - With Powered Convenience Outlet (with VFD)
Compressor 1
Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating
/ Pwr Exh
Si
ze
(T
on
s)
N
om
in
al
U
ni
t V
ol
ta
ge
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA
(Amps)
2, 3
Min Fuse
/ Breaker
Size (Amps)
Max Fuse
/ Breaker
Size (Amps)
FLA LRA
MCA
w/Pwr Exh (Amps)
Min Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
Max Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
FLA LRA
None
-
-
-
49.6
50
60
53 262
51.8
60
60
56 272
11725 12
1
33.3
59.4
60
60
55 262
62.1
70
70
57 272
12525 18.6
1
51.6
82.3
90
90
76 262
85
90
90
78 272
13225 24
1
66.6
101
110
110
93 262
103.8
110 110 95 272
208-3-60 13.7 83.1 21 13.7 83.1 21
2.3
9.9
1.1
8.6
14225 31.8
2
88.3
128.1
150
150
118 262
130.9
150 150 120 272
None
-
-
-
49.1
50
60
53 271
51.1
60
60
55 266
11725 16
1
38.5
65.3
70
70
60 271
67.8
70
70
62 266
12525 24.8
1
59.7
91.8
100
100
84 271
94.3
100 100 87 266
13225 32
1
77
113.4
125
125
104 271
115.9
125 125 107 266
230-3-60 13.7 83.1 21 13.7 83.1 21
2.3
9.4
1
8.6
14225 42.4
2
102
144.6
150
150
133 271
147.1
150 150 135 266
None
-
-
-
23.5
25
25
25 136
24.5
25
25
26 132
11746 16.5
1
19.8
33.3
35
35
31 136
34.6
35
35
32 132
12846 27.8
1
33.4
50.3
60
60
46 136
51.6
60
60
47 132
13346 33
1
39.7
58.2
60
60
54 136
59.4
60
60
55 132
460-3-60 6.2 41
10
6.2 41
10
1.3
4.7
0.5
8.6
14246 41.7
2
50.2
71.3
80
80
66 136
72.6
80
80
67 132
None
-
-
-
19
20
20
20 117
19.8
20
20
21 114
11758 17
1
16.4
28
30
30
26 117
29
30
30
27 114
09 (8.5)
575-3-60 4.8 33
8
4.8 33
8
1.1
4.3
0.4
8.6
13458 34
1
32.7
48.4
50
50
45 117
49.4
50
50
45 114
None
-
-
-
59.6
60
70
64 349
61.8
70
70
66 359
11725 12
1
33.3
63.9
70
70
64 349
66.6
70
70
66 359
12525 18.6
1
51.6
86.8
90
90
80 349
89.5
90
90
82 359
13225 24
1
66.6
105.5
110
110
97 349
108.3
110 110 100 359
208-3-60 16 110 25
16 110
25
5.8
13.5
1.1
8.6
14225 31.8
2
88.3
132.6
150
150
122 349
135.4
150 150 125 359
None
-
-
-
58.9
60
70
63 345
60.9
70
70
65 350
11725 16
1
38.5
70.3
80
80
65 345
72.8
80
80
67 350
12525 24.8
1
59.7
96.8
100
100
89 345
99.3
100 100 91 350
13225 32
1
77
118.4
125
125
109 345
120.9
125 125 111 350
230-3-60 16 110 25
16 110
25
5.2
13.4
1
8.6
14225 42.4
2
102
149.6
150
150
138 345
152.1
175 175 140 350
None
-
-
-
29.4
30
35
32 168
30.4
35
35
33 170
11746 16.5
1
19.8
35.8
40
40
33 168
37.1
40
40
34 170
12846 27.8
1
33.4
52.8
60
60
49 168
54.1
60
60
50 170
13346 33
1
39.7
60.7
70
70
56 168
61.9
70
70
57 170
460-3-60 7.8 52
12
7.8 52
12
2.9
6.7
0.5
8.6
14246 41.7
2
50.2
73.8
80
80
68 168
75.1
80
80
69 170
None
-
-
-
22.1
25
25
24 131
22.9
25
25
25 133
11758 17
1
16.4
29.4
30
30
27 131
30.4
35
35
28 133
12 (10)
575-3-60 5.7 38.9
9
5.7 38.9
9
2.2
5.4
0.4
8.6
13458 34
1
32.7
49.8
50
50
46 131
50.8
60
60
47 133
1
Minimum Circuit Ampacity.
2
Dual Element, Time Delay Type.
3
HACR type per NEC.
4
Non-fused Disconnect. Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field
installed electric heat kits may exceed the factory installed disconnect amperage rating.
INSTALLATION MANUAL ZY SERIES 3 - 10 ton 60 Hertz R-410A
62
Johnson Controls Ducted Systems
Summary of Contents for ZY Series
Page 2: ...2 INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 140: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 140 Johnson Controls Ducted Systems ...
Page 141: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 141 Johnson Controls Ducted Systems ...
Page 142: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 142 Johnson Controls Ducted Systems ...
Page 143: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 143 Johnson Controls Ducted Systems ...