Table 9: ZY04 to 12 Standard Static Indoor Blower - Without Powered Convenience Outlet
Compressor 1
Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating
/ Pwr Exh
Si
ze
(T
on
s)
N
om
in
al
U
ni
t V
ol
ta
ge
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA
(Amps)
2, 3
Min Fuse
/ Breaker
Size (Amps)
Max Fuse
/ Breaker
Size (Amps)
FLA LRA
MCA
w/Pwr Exh (Amps)
Min Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
Max Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
FLA LRA
None
-
-
-
48.8
50
60
52 302
51
60
60
54 312
11725 12
1
33.3
50.4
60
60
52 302
53.1
60
60
54 312
12525 18.6
1
51.6
73.3
80
80
67 302
76
80
80
70 312
13225 24
1
66.6
92
100
100
85 302
94.8
100 100 87 312
208-3-60 16 110 25
16 110
25
5.8
7
1.1
14225 31.8
2
88.3
119.1
125
125
110 302
121.9
125 125 112 312
None
-
-
-
48.4
50
60
51 301
50.4
60
60
53 305
11725 16
1
38.5
57.1
60
60
53 301
59.6
60
60
55 305
12525 24.8
1
59.7
83.6
90
90
77 301
86.1
90
90
79 305
13225 32
1
77
105.3
110
110
97 301
107.8
110 110 99 305
230-3-60 16 110 25
16 110
25
5.2
7.2
1
14225 42.4
2
102
136.5
150
150
126 301
139
150 150 128 305
None
-
-
-
24.1
25
30
25 146
25.1
30
30
27 148
11746 16.5
1
19.8
29.3
30
30
27 146
30.5
35
35
28 148
12846 27.8
1
33.4
46.3
50
50
43 146
47.5
50
50
44 148
13346 33
1
39.7
54.1
60
60
50 146
55.4
60
60
51 148
460-3-60 7.8 52
12
7.8 52
12
2.9
3.6
0.5
14246 41.7
2
50.2
67.3
70
70
62 146
68.5
70
70
63 148
None
-
-
-
17.5
20
20
19 107
18.3
20
20
19 109
11758 17
1
16.4
23.6
25
25
22 107
24.6
25
25
23 109
12 (10)
575-3-60 5.7 38.9
9
5.7 38.9
9
2.2
2.5
0.4
13458 34
1
32.7
44
45
45
40 107
45
45
45
41 109
1
Minimum Circuit Ampacity.
2
Dual Element, Time Delay Type.
3
HACR type per NEC.
4
Non-fused Disconnect. Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field
installed electric heat kits may exceed the factory installed disconnect amperage rating.
INSTALLATION MANUAL ZY SERIES 3 - 10 ton 60 Hertz R-410A
34
Johnson Controls Ducted Systems
Summary of Contents for ZY Series
Page 2: ...2 INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 140: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 140 Johnson Controls Ducted Systems ...
Page 141: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 141 Johnson Controls Ducted Systems ...
Page 142: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 142 Johnson Controls Ducted Systems ...
Page 143: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 143 Johnson Controls Ducted Systems ...