SECTION 6 – USER INTERFACE CONTROL CENTER
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
6
TABLE 29 -
COOLING
DISPLAY TEXT
PASS
WORD
LEVEL
RANGE
DEFAULT
SHOW WHEN UNIT TYPE IS
Supply Air Temp
Current
-20.0º F TO 180.0º F
Look up table
UNIT TYPE equals CONSTANT VOL-
UME or VARIABLE AIR VOLUME
Active Sp
1
50.0º F TO 65.0º F
Derived
Mixed Supply Air Temp
Current
-20.0º F TO 180.0º F
Look up Table
UNIT TYPE equals FLEXSYS
Active Sp
1
50.0º F TO 65.0º F
65.0º F
Flex Evap Temp
Current
-20.0º F to 180.0º F
Look up Table
UNIT TYPE equals FLEXSYS and
Current Oper Mode is OCC COOLING
W/BYP
Active Sp
1
50.0º F to 65.0º F
65.0º F
Cooling Control Offset
1.0º F to 100.0º F
Derived
Always
Return Air Diff SP
6.0º F
Return Air Diff Active
6.0º F
Zone Temp
Current
-20.0º F to 180.0º F
Look up table
UNIT TYPE equals CONSTANT VOL-
UME or UNIT MODE is OCCUPIED
OCC Zone Cooling
Setpoint
1
OCC Zone Heating Plus
2.0º F to 85.0º F
72.0º f
Zone Temp
Current
-20.0º F TO 180.0º F
Look up table
Unit is UNOCCUPIED and NIGHT SET
BACK is ENABLED
Unocc Zone Cooling
Setpoint
1
UNOCC Zone Heating
Plus 2.0º F to 95.0º F
85.0º f
Return Air Temp
Current
-20.0º F to 180.0º F
Look up table
UNIT TYPE equals VARIABLE AIR
VOLUME or FLEXSYS
Rat Cooling Setpoint
1
RAT heating setp
PLUS2º F to rat for high
sat
70.0º f
Return Air Bypass
Current
0 to 100%
Derived
UNIT TYPE equals FLEXSYS
Active Sp
0 to 100%
Derived
Bypass Damper Position
0 to 100%
Derived
UNIT TYPE equals FLEXSYS
Underfloor Air
Temp
-20.0º F to 180.0º F
Look up table
UNIT TYPE equals FLEXSYS and Dew
Point Reset equals ENABLED
Humidity
0 to 100%
Derived
Underfloor Slab
Temp
-20.0º F to 180.0º F
Look up table
UNIT TYPE equals FLEXSYS and Dew
Point Reset equals ENABLED
Dew Point
30.0º F to 100.0º F
Derived
Need to Dehumidify
Yes/No
UNIT TYPE equals FLEXSYS and
Heating System Type is ELECTRIC
and ENABLED
Under Floor Temp OVRD
Active - Inactive
Derived
Active Slab Control is USER EN-
ABLED
Reset Enthalpy SP
30.00 BTU#
Reset Enthalpy Active
30.00 BTU#