SECTION 6 – USER INTERFACE CONTROL CENTER
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
6
PROGRAM
To view the values press the PROGRAM key. After
pressing the PROGRAM key use the ◄ key or the
► key to select the menu subsection: Unit, Cooling,
Compressor Systems, Supply System, Heating, Econo-
mizer, Ventilation, or Condenser, that contains the pa-
rameter you would like to view. The parameters con-
tained under each of these menu subsections and their
password level is contained in
▲
and
▼
arrow key to navigate to the parameter within the
subsection you want to view.
If you need to change any of the “Program” parameters
press the CHECK key. The Enter Password screen ap-
pears. All “Program” parameters require the use of a
password before they can be changed.
on page 168 for information on how to enter a pass-
word into the User Interface.
If a Level 1 password is
entered, only Level 1 “Program” parameters are avail-
able for change. Entering a Level 2 password makes all
“Program” parameters available.
Once a password is entered it remains active for 15
minutes.
TABLE 37 -
PROGRAM
USER
INTERFACE
KEY
SUBSECTION
DISPLAYED TEXT
RANGE
DEFAULT
VALUE
UNIT
SETTING
Program
Unit Data
Display Language
English / Spanish
2
English
Program
Unit Data
Display Units
Imperial / Metric
Imperial
Program
Unit Data
Control Method
1
Wire Zone Temp /
Comm Zone Temp
Wire Zone
Temp
Program
Unit Data
Clock Schedule
User Enabled /
User Disabled
User Disabled
Program
Unit Data
Isolation Damper Control
User Enabled /
User Disabled
User Disabled
Program
Cooling
Active Slab Control
User Enabled / User Disabled
User Disabled
Program
Cooling
Dew Point Reset
User Enabled / User Disabled
User Disabled
Program
Cooling
Sat Reset Method
None / Outside Air / Return Air /
Supply Fan Speed
Returned Air
Program
Cooling
Sup Air Tempering
User Enabled / User Disabled
User Disabled
Program
Cooling
Undr Flr Humi Bas
User Enabled / User Disabled
User Disabled
Program
Cooling
Undr Flr Temp Bas
User Enabled / User Disabled
User Disabled
Program
Cooling
FlexSys Reheat
User Enabled / User Disabled
User Disabled
NOTES:
1. If Night Setback is Enabled, there must be either a Hardwired or Communicated Zone Temp Value present. If there is no Zone Temp value,
it is set for Hardwired and Night Setback is Enabled, the unit will fault and shutdown. Control Method will only display when in Constant
Volume. If the unit is shipped as VAV or FlexSys you need to change the Unit Type to Constant Volume and change the Control Method to
Communicated Zone Temperature control. Return to the VAV or FlexSys mode. Control Method only shows in the Constant Volume mode.
2. Spanish is a future option. It may not currently be available.