SECTION 6 – USER INTERFACE CONTROL CENTER
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
6
TABLE 42 -
BACNET MS/TP, MODBUS, BACNET IP (CONT'D)
BACNET
NAME
USER INTERFACE
NAME
READ/
WRITE
BACNET
OBJECT
TYPE AND
INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
UNIT_STOP
Unit Stop
R/W
AV93,
BV17
1118
This Command Allows the Unit to Be Shut
Down Through The Bas System (0 = Normal
Operation/ 1 = Stopped
UNOCC_ZN_
COOL
Unoccupied Zone Cool-
ing
R/W
AV38
1063
The Unoccupied Zone Cooling Setpoint (F)
UNOCC_ZN_
HEAT
Unoccupied Zone Heat-
ing
R/W
AV39
1064
The Unoccupied Zone Heating Setpoint (F)
VAV_HEAT
VAV Heat
R
BI61
1342
Identifies the Status of the Binary Output
TP
Energize a VAV Heat Relay (Off / On)
VENT_EN-
ABLE
Ventilation Enable
R/W
AV95,
BV19
1120
This Command Allows the Ventilation Func-
tion to be Turned On or Off (0 = Off / 1 = On)
VENT_STAT
Vent Sys Status
R
AI89
602
Identifies the Status of the Ventilation System
(0 - Normal - Inactive; 1 - Normal - Active; 3 -
None; 4 - Disabled)
WTR_ECN_
DLTA
Water Econo Delta
R/W
AV44
1069
This Item is Used in the Determination of
when Waterside Economizer becomes Active
(F)
WTR_ECN_
MIN
Water Econo Min Pos
R/W
AV45
1070
The Minimum Allowable Opening for the
Water Economizer Valve (%)
WTR_
FLOW_SW
Water Flow Switch
R
BI71
1352
Identifies if a Water Flow Switch is Installed
ENA = Not Installed
DIS = Installed
WTR_TEMP_
ENT
Water Temp Entering
R
AI90
603
The Temperature of the Condenser Water
Entering the Unit
WTR_TEMP_
LEV
Water Temp Leaving
R
AI91
604
The Temperature of the Condenser Water
Leaving the Unit
ZONE_TEMP
Zone Temp
R
AI60
573
Zone Temperature the Control is Controlling
to (F)
ZONE_TMP_
BAS
Zone Temp BAS
R/W
AV40
1065
This Allows the BAS System to Input a Zone
Temperature Value to the Control on a Con-
stant Volume Unit with Communicated Zone
Control (F)
NOTE:
The most recent listing of the standard points mapping can be found in the Johnson Controls website.