JOHNSON CONTROLS
206
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
SECTION 8 – SERVICE
TABLE 51 -
FAULT AUTO - RESET
HISTORY SCREEN
WORDING
DESCRIPTION
RESET
SHOW WHEN
UNIT TYPE IS
STATUS
SCREEN
WORDING
FAULT
OUTPUT
TYPE
Auto Reset-Com-
pressor System *
Clear
See description below
Auto
Reset
Auto Reset-
Compress System *
Trip 1
The safety input chain is open (faulted) for
more than two seconds with the compres-
sor of the system on, and this is the first
trip in a 120 minute span
Auto
Reset
Comp system
* status
safety trip
Alarm
Auto Reset
Compressor
System * Trip 2
The safety input chain is open (faulted) for
more than two seconds with the com-
pressor of the system on, and this is the
second trip in a 120 minute span
Auto
Reset
Comp system
* status
safety trip
Alarm
Auto Reset -
MSAT Sensor
MS supply air temp current sensor is out
of range for greater than or equal to 10
seconds
Auto
Reset
UNIT TYPE is
FLEXSYS
Alarm
Auto Reset - Power
Fail
Power is lost when the unit operating
state is RUN
Auto
Reset
Auto Reset -
RAT Sensor
Return air temp current sensor is out
of range for greater than or equal to 10
seconds
Auto
Reset
Alarm
Auto Reset - Re-
mote I/O Comm
No communication from the I/O board for
greater than or equal to 5 seconds
Auto
Reset
Auto Reset - Zone
Temp Sensor
Zone temp current sensor is out of range
for greater than or equal to 10 seconds. If
Night Setback is ENABLED and there is
not a valid zone temp sensor value when
the unit goes UNOCCUPIED, a fault be-
comes active and prevents the unit from
starting.
Auto
Reset
UNIT TYPE is VAV
and NIGHT SET
BACK is USER
ENABLED or UNIT
TYPE is set to CV
and the CONTROL
METHOD is set to
ZONE SENSOR
HARDWIRED
Alarm