JOHNSON CONTROLS
36
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
SECTION 2 – INSTALLATION
TABLE 5 -
OPERATING WEIGHTS (LSW_025–060)
MODEL
025
032
035
040
050
060
Coil Section
1,832
1,890
1,941
2,032
3,536
3,656
Water Economy Coil Option
320
378
442
442
711
711
High Efficiency Option
20
25
30
45
70
80
Fan Section
984
984
984
984
1,380
1,380
Supply Fan
25 Inch Class II
N/A
358
358
358
N/A
N/A
28 Inch Class II
273
273
273
273
N/A
N/A
32 Inch Class II
N/A
N/A
N/A
N/A
427.9
428
36 Inch Class II
N/A
N/A
N/A
N/A
582.59
583
40 Inch Class II
N/A
N/A
N/A
N/A
N/A
N/A
Filter Section
4 inch 30-35% Efficiency (MERV 8)
156
156
156
156
205
205
4 inch 60-65% Efficiency (MERV 11)
178
178
178
178
265
265
4 inch 60-65% Eff + 4 inch 30-35% Eff Prefilter
(MERV 11 + 8)
288
288
288
288
391
391
4 inch 90-95% Eff + 4 inch30-35% Eff Prefilter
(MERV 14 + 8)
288
288
288
288
391
391
Plenums
Inlet Plenum - Sound Attenuating
246
246
246
246
290
290
Air Economizer
678
678
678
678
866
866
Outlet Plenum - Half
295
295
295
295
355
355
Outlet Plenum - Full
386
386
386
386
415
415
TABLE 6 -
SUPPLY FAN MOTOR WEIGHTS
HP
ODP
TEFC
HI-EFF
PREMIUM EFF
HI-EFF
PREMIUM EFF
5 HP
160
175
169
199
7.5 HP
193
207
219
260
10 HP
220
238
239
341
15 HP
327
327
349
365
20 HP
317
367
389
421
25 HP
385
470
572
538
30 HP
427
512
580
573
40 HP
532
614
595
742
50 HP
540
622
729
900
60 HP
637
848
877
964
NOTES:
1. All weights are in Lbs.
2. Add waterside economizer weight, if selected, to coil section.
3. Add selected fan, motor, and VFD weight to the fan section weight to get total fan weight.
4.
Add coil section, fan section and filter section weights together to obtain total unit weight.