SECTION 6 – USER INTERFACE CONTROL CENTER
BACNET
NAME
USER INTERFACE
NAME
READ/
WRITE
BACNET
OBJECT
TYPE AND
INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
COND_PRS_
OUT
Condenser Pressure PI
Output
R
AI75
588
This is a Derived Value that Identifies the
Output Demand to the Condenser Water
Valve (%)
COND_TYPE
Condenser Type
R
AI76
589
This Identifies the Type of Condenser In
-
stalled in the Unit (0 = Water Cooled; 1 = Air
Cooled)
COND_VAL_
INS
Cond Valves Install
R
AI72
585
Identifies the Condenser Valve Installed (0 =
None; 1 = Cond Only; 2 = Cond W/Bypass)
COND_
WTR_CNT
Cond Water Control
R
BI66
1347
Identifies the Status of the Condenser Water
Control ( 0 = Dis; 1 = Ena)
COND_
WTR_FLW
Cond Water Flow
R
AI73
586
Identifies if the Unit is Configured for a Water
Flow Switch (0 = None; 1 = Installed)
COND_
WTR_VAL
Cond Water Valve
R
AI74
587
Shows the Position of the Condenser Water
Valve (%)
DCT_STAT_
PR1
Duct Static Pres 1
R
AI17
530
Actual Duct Static Pressure Input from Trans-
ducer 1 to the Control ("WG)
DCT_STAT_
PR2
Duct Static Pres 2
R
AI77
590
Actual Duct Static Pressure Input from Trans-
ducer 2 to the Control ("WG)
DEW_PNT_
RST
Dew Point Reset
R/W
BV4
1105
This Allows the Dew Point Reset Feature to
be Turned On and Off on FlexSys Units (0 =
Off / 1 = On)
DSP_HI_SP
Duct Static High Setp
R/W
AV03
1028
The Duct Static Upper Setpoint ("WG)
DSP_LO_SP
Duct Static Low Setp
R/W
AV04
1029
The Duct Static Lower Setpoint ("WG)
DSP_RST_
BAS
Duct Static Pres Rst
Bas
R/W
AV05
1030
A BAS Entered Value that Results in a
%Reset Down from the Duct Static High Limit
Based on a Percent of the Difference Be-
tween Duct Static High Limit and Duct Static
Low Limit (%). “DUCT PRES RST BAS” Must
be Enabled Using the Service Key to Use
this Feature
ECON_ME_
USED
Economizer Method
Active
R
AI18
531
The Economizer Method being Used by the
Control (1 - Dry Bulb; 2 - Single Enthalpy; 3 -
Dual Enthalpy; 4 - Best Method; 5 - Waterside)
ECONO_IN-
STAL
Economizer Installed
R/W
BV5, AV81
1106
Allows the Economizer Feature to be Turned
On and Off (0 = Off / 1 = On)
ECONO_
METHOD
Econo Method To Use
R/W
AV06
1031
The Economizer Method Selected for Use
(0 - None; 1 - Dry Bulb; 2 - Single Enthalpy; 3
- Dual Enthalpy; 4 - Best Method; 5 - Water-
side)
ECONO_
VALVE
Economized Valve
Position
R
AI16
529
Current Output Value to the Waterside
Economizer Valve from the Unit Controller.
ECON_STA-
TUS
Econo Sys Status
R
AI19
532
Status of the Economizer Option (0 - Normal
Inactive; 1 - Normal Active; 2 - None; 3 - Dis-
abled; 8 - Safety Lockout)
ECON_
METHOD
Econo method to use
R/W
AV06
1031
The Economizer Method Selected for Use
(0 - None; 1 - Dry Bulb; 2 - Single Enthalpy; 3
- Dual Enthalpy; 4 - Best Method; 5 - Water-
side)
TABLE 42 -
BACNET MS/TP, MODBUS, BACNE IP (CONT'D)