SECTION 2 – INSTALLATION
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
FIGURE 55 -
CTB1 FIELD CONTROL WIRING
Wiring Notes:
1. Wiring shown indicates typical wiring.
2. All wiring is Class 2, low voltage.
3. Maximum power available from the 24VAC terminal is 40VA.
4. Use shielded wire where shown.
5. Relay contacts suitable for pilot duty to 1A from 24VAC to 120VAC.
6. Wire 261 must be removed from the SD terminal and connected to one side of a field installed normally closed contact. The other side of the
normally closed contact is connected to the SD terminal.
LD13325 mod
PUMP START
ALARM
VAV HEAT
Zone Temp. Sensor
FlexSys Slab Temp. Sensor
Caution: 24 VAC switch voltage must
be sourced from the unit. Use of
another power source external of the
unit may cause equipment damage
.
Remote Shutdown
Open = Shutdown
Closed = Run
Closed = Occupied
Open = Unoccupied
Contacts Close When
VAV Boxes Should
Open
261
See Note 6