IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
45
Point Program
Program
Figure 3.32 Module Point Programming Screen 2 (Monitor)
Soft Keys
CUSTOM ACTION MESSAGE:
Displays the custom action message number (a value of one
through 100). The default value is 0 (no message). Press this soft key to progress to the Custom
Action Message screen (shown in Figure 3.27) to view the message or to choose a different
message for viewing when this point activates. (To create a new custom action message, refer to
“Custom Action Message” on page 35.)
ZONE MAP:
Displays the zones mapped to this point. During initial programming, zone map
position one for each monitor module is set to Z0YY, where YY represents the loop number where
the module resides. In Figure 3.32 above, zone position one has a value of Z003 (YY = 03). The
module in the example resides on loop 3.
To add or delete zones, press this soft key to proceed to the Module Zone Map screen. Refer to
“Zone Map” on page 39 for an illustration and explanation of the Detector Zone Map screen. The
Module Zone Map screen is the same except that Module replaces Detector in the title and the
module address appears instead of the detector address. Up to ten general, releasing or special
zones may be mapped to a monitor module: none of the zone map positions are fixed. Position 1
has additional functionality.
Position 1 - This position is checked when a group zone disable command is issued. If the zone
number in the group zone disable command matches the zone number in the first position of
the zone map, the module point will be disabled.
ALARM VERIFICATION:
Press this key to determine participation in Alarm Verification.
Choosing Yes will set the device participation to the value entered at the Panel Timers screen
(Figure 3.8). The only module type that can participate in alarm verification is the M302MJ.
LOCAL MODE:
Press to toggle between Local Mode (
ON
) or no Local Mode (
OFF
). When there is
a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected
for Local Mode participation (
ON
) will continue to function across all the panel’s SLCs in a limited
manner as follows: input points will activate output points of the same Type Code point type
designations. For example, SLC inputs with“fire” point types will activate SLC outputs with“fire”
point types. Refer to “Type Codes for Input Devices” on page 134 for Type Code point types.
Default: OFF
NOTE:
The panel setting
LCM
LOCAL
MODE
must be set to Yes for local mode to work at the
device level.
ACCEPT:
Press to save entries made on this screen and to return to the previous screen.
M O D U L E P O I N T P R O G R A M M I N G
L 0 3 M 1 2 3
C U S T O M A C T I O N M E S S A G E : 0 2 0
Z O N E M A P :
Z 0 0 3
, Z 1 0 4
, Z 1 0 5
, Z 1 0 6
, Z 1 0 7
Z 1 1 0
, Z 1 1 4
, Z 1 1 5
, Z 1 1 6
, Z 1 1 7
A L A R M V E R I F I C A T I O N : O F F
L O C A L M O D E : O F F
A C C E P T
B A C K
Zone Map Position 1 - Use for group zone
disable participation.
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...