IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
39
Point Program
Program
Zone Map
The Detector Zone Map screen will display when the
ZONE
MAP
soft key is pressed at the Detector
Point Programming screen.
Figure 3.25 Zone Map (Detector Point) Screen
The point address will appear in line 3 of the screen.
Refer to “CBE: Zones and Equations” on page 125, and “Special Zone Outputs” on page 113 in this
manual for more information about zones and how they apply to Control-By-Event.
Soft Keys
ZONE
MAP:
A detector may be mapped to up to ten general, releasing, or special zones. There are
ten positions available for mapping; positions 1, 9 and 10 - refer to Figure 3.25 - have additional
functionality.
Position 1 - Use this position to link the 20-character zone label to the detector. The zone label
will appear after the 20-character label and 12-character extended label, providing a total of 52
characters to describe an event.
This position is checked when a group zone disable command is issued. If the zone number in
the group zone disable command matches the zone number in the first position of the zone
map, the detector point will be disabled.
Position 10 - Use this position to map detectors with an “Action” Prealarm setting. The zone in
the tenth position will activate when the detector reaches its Prealarm threshold; no other zones
in this detector’s zone map will activate.
Position 9 -
• Use this position to activate the sounder/relay base of a detector. When this position is
mapped to the same zone as Position 10, the sounder or relay base will be activated when
the detector goes into prealarm (Action).
• Use this position to activate the sounder base of a detector using a general or a logic zone.
When a general or logic zone activates, the panel is searched for any detector with the same
zone mapped in its 9th position. The sounder base of any detector that matches the search
will activate.
Move the cursor with the keyboard arrow keys to the appropriate zone map position, then select the
type of type of zone by pressing the
NEXT
SELECTION
(+) key until the desired zone type appears.
Type in a zone number to map the detector to it.
Zone Map
Position
2
3
4
5
6
7
8
D E T E C T O R Z O N E M A P
L 0 3 D 1 2 3
Z O N E S E L E C T I O N
Z 0 0 3 ,
( Z O N E )
Z 1 8 7 ,
( Z O N E )
Z 2 3 4 ,
( Z O N E )
Z X X X
( U N M A P P E D )
Z X X X
( U N M A P P E D )
Z X X X
( U N M A P P E D )
Z X X X
( U N M A P P E D )
Z X X X
( U N M A P P E D )
Z X X X
( U N M A P P E D )
A C C E P T
Z X X X
( U N M A P P E D )
B A C K
Zone Map Position 10 - Use for
detectors set to Prealarm, Action.
Zone Map
Position 9 - Use
to activate
sounder/relay-
bases.
Zone Map
Position 1 -
Use to link
zone label
to detector,
and for
group zone
disable.
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...