134
IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
Type Codes
Type Codes for Input Devices
G.3 Type Codes for Input Devices
G.3.1 Overview
This section provides a list of Type Codes for intelligent detectors and for monitor modules. The
following Point Types light an LED at the panel when activated.
• fire alarm - lights the
FIRE ALARM
LED
• supervisory - lights the
SUPERVISORY
LED
• security - lights the
SECURITY
LED
• trouble - lights the
TROUBLE
LED
G.3.2 Type Codes for Intelligent Detectors
Following is a list of intelligent detector Type Codes, which specify the type of detector installed at
an SLC address.
Table G.1 Intelligent Detector Type Codes
Point Characteristics
Type Code
Point Type
Latching
(Y=yes
N=no)
Activates
CBE
Device/Point Function
SMOKE (ION)
fire
Y
Y
Ionization smoke detector
SUP L(ION)
*
supervisory
Y
Y
Ionization smoke detector
†
supervisory
N
Y
Ionization smoke detector
SMOKE(DUCTI)
fire
Y
Y
Duct Ionization smoke detector
SUP L(DUCTI)
supervisory
Y
Y
Duct ionization smoke detector
supervisory
N
Y
Ionization smoke detector used as a duct detector to report
supervisory condition rather than alarm.
SMOKE(PHOTO)
fire
Y
Y
Photoelectric smoke detector
SUP L(PHOTO)*
supervisory
Y
Y
Photoelectric smoke detector
SUP T(PHOTO)*†
supervisory
N
Y
Photoelectric smoke detector
SMOKE(DUCTP)
fire
Y
Y
Duct Photoelectric smoke detector
SUP L(DUCTP)
supervisory
Y
Y
Photoelectric smoke detector used as a duct detector to report
supervisory condition rather than alarm
supervisory
N
Y
Photoelectric smoke detector used as a duct detector to report
supervisory condition rather than alarm.
RFSMOKE(PHOTO)
fire
Y
Y
Wireless Photoelectric smoke detector
SMOKE(HARSH)
fire
Y
Y
HARSH smoke detector
SMOKE(LASER)
fire
Y
Y
Laser smoke detector
SUP T (LASER)*†
supervisory
N
Y
Laser Smoke Detector
SUP L (LASER)*
supervisory
Y
Y
Laser Smoke Detector
AIR REF
fire
Y
Y
Assign to one or more
7351J detectors used to monitor the quality of
air entering the protected area. The air quality measurement allows
the
VIEW® system to compensate for vehicle fumes, fog, or other
particles brought into the protected area through the ventilation
system. Poor air quality will lower the sensitivity of all
7351J detectors
on the SLC. The detector sensitivity, however, remains within
approved limits (always less than 1% obscuration per foot).
Note: A reference detector still functions as a smoke detector, but the detector sensitivity level should be set to the least sensitive level—AL:9 and
PA:9 Alarm and Pre-Alarm sensitivity. Refer to “Detector Sensitivity Settings” on page 119 for a complete list of detector sensitivity settings.
HEAT
fire
Y
Y
190
o
F heat detector
HEAT+
fire
Y
Y
190
o
F heat detector with low temperature warning
HEAT(FIXED)
fire
Y
Y
135
o
F intelligent thermal sensor
HEAT (ROR)
fire
Y
Y
15
o
F per minute rate-of-rise detector
SMOKE ACCLIM
fire
Y
Y
Combination Photoelectric/heat detector
SMOKE(ACCLI+)
fire
Y
Y
Combination Photoelectric/heat detector with low temperature
warning
SMOKE(MULTI)
‡
fire
Y
Y
Multisensor smoke detector
SMOKE(BEAM)
fire Y
Y
Beam
Smoke
Detector
*
Use only with approval of AHJ
† Not suitable for Canadian applications
‡ CLIP Mode only
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...