IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
49
Point Program
Program
Point Programming (2) - Monitor
Figure 3.36 Panel Module Point Programming (2) -Monitor - Screen
Soft Keys
CUSTOM ACTION MESSAGE:
Displays the custom action message number (a value of one
through 100). The default value is 0 (no message). Press this soft key to progress to the Custom
Action Message screen (shown in Figure 3.27) to view the message or to choose a different
message for viewing when this point activates. (To create a new custom action message, refer to
“Custom Action Message” on page 35.).
ZONE MAP:
Displays the zones mapped to this point. The default value assigned to panel circuit
input modules during initial programming is Z011 in the first zone map position.
To add or delete zones, press this soft key to proceed to the Panel Module Zone Map screen. Refer
to “Zone Map” on page 39 for an illustration and explanation of the Detector Zone Map screen. The
Panel Module Zone Map screen is the same except that Panel Module replaces Detector in the title
and the module address appears instead of the detector address. Up to ten general, releasing or
special zones may be mapped to a panel monitor module. Position 1 has additional functionality.
Position 1 - This position is checked when a group zone disable command is issued. If the zone
number in the group zone disable command matches the zone number in the first position of
the zone map, the module point will be disabled.
ALARM VERIFICATION:
Press this key to determine participation in Alarm Verification.
Choosing Yes will set the device participation to the value entered at the Panel Timers screen
(Figure 3.8).
ACCEPT:
Press to save entries made on the screen and return to the previous screen.
P A N E L M O D U L E P O I N T P R O G R A M M I N G
P 1 0 . 2
C U S T O M A C T I O N M E S S A G E : 0 2 0
Z O N E M A P :
Z 0 1 1
, Z 1 0 4
, Z 1 0 5
, Z 1 0 6
, Z 1 0 7
Z 1 1 0
, Z 1 1 4
, Z 1 1 5
, Z 1 1 6
, Z 1 1 7
A L A R M V E R I F I C A T I O N : O F F
A C C E P T
B A C K
Position 1 - Use for group zone disable participation.
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...