122
IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
AWACS™ Applications
Detector Status Display
D.5.2 Print a Detector Maintenance Report
A Detector Maintenance Report lists detector maintenance status for each installed addressable
detector [except 5551J/5551JR (analog heat detector)].
To print this report, press the Printer Function soft key at the Main Menu, then press the Detector
Maintenance Report soft key sends a Detector Maintenance Report (Figure D.7) to the printer
connected to the control panel.
Figure D.7 Sample Detector Maintenance Report
D.5.3 To Interpret a Detector Status Display or Maintenance Report
The Detector Read Status Screen and Detector Maintenance Report provides the same information
(such as Device Status, Peak Value) about a detector. This section contains descriptions of each
item that appears in a Detector Read Status Screen or a Detector Maintenance Report.
Display Information
Lines 1- 4 - This could display any current event message, or, as in this example, the System
Normal message
Line 5 - Screen title and the address of the point being read
The area between the separator lines, lines 6-14, shows all information concerning the selected
point, which is L03D052 in the above example.
Line 6 - Line 6 displays two statistics that display for inputs (detectors and modules) and zones; in
the above example they are:
AUTOMATIC
INACTIVE
******DETECTOR MAINTENANCE******************************************************
NORMAL SMOKE(LASER) Detector
L01D001 000330us 000340us
Comp:000% Pk: 002%
Alarm:
000% PreAlarm:
000% A6P6 V000
L01D001
NORMAL SMOKE ACCLIM Detector
L01D002 000030us 000000us
Comp:000% Pk: 000%
Alarm:
000% PreAlarm:
000% A8P8 V000
L01D002
Field Identification
State
Label
Extended
Label
Current reading of raw analog
value in microseconds
Long term average of
raw analog value in
microseconds
Compensation
percentage
Detector peak
Address
Percent of
alarm
threshold
Percent of
prealarm
threshold
Verification count
Programmed alarm sensitivity setting in
effect when the report was generated.
Programmed prealarm sensitivity setting in
effect when the report was generated
Alarm:
000% PreAlarm:
000% A6P6 V000
L01D001
NORMAL SMOKE(LASER) Detector
L01D001 000330us 000340us
Comp:000% Pk: 002%
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...