110
IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
Releasing Applications
Abort Switches
How to Program an Instant Release Circuit
The following contains information needed to program an Instant Release circuit for an SLC output
module
.
NOTE:
An output with an
INST RELEASE
Type Code requires the following selections: a zone
selection (a releasing zone may be used, but is not required); an output circuit mapped to the
same zone; Switch Inhibit; Non-Silenceable; No Walk Test.
Description
An SLC output circuit module programmed to activate non-releasing devices, such as door
openers or warning sounders, without counting down delay timers. A device programmed with
the
INST RELEASE
Type Code device is supervised for open circuits and ground faults.
Program
Select an SLC output module to use with a releasing circuit. While programming the point (refer
to the Point Programming section of this manual for instructions),
1.
Select the
INST RELEASE
Type Code,
2.
Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).
Example
A programming example of a control module programmed as an Instant Release circuit for Releasing Zone
ZR05.
Figure B.18 Output Module Configured as an Instant Release Circuit
Type Code
INST RELEASE
ZR05
Monitor
Module
Detector
Detector
Detector
Type Code
INST RELEASE
For example, a module programmed with the
INST RELEASE
Type Code activates simultaneously with other outputs
(modules A & B) programmed for ZR05.
SLC
output
module
A
SLC
output
module
B
SLC
output
module
SLC
output
module
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...