136
IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
Type Codes
Type Codes for Output Devices
G.4 Type Codes for Output Devices
This section provides a list of Type Codes for SLC control module points and panel circuit output
module points. Select from these codes to define the type of point..
Table G.3 SLC Control Module and Panel Circuit Output Module Type Codes
NOTE:
Do not assign Releasing Type Codes to Panel Circuit module points
.
Type Code
Silenceable
(Y=yes
N=no)*
Switch
Inhibit
(Y=yes,
N=No)
*
Walk Test
(Y=yes,
SLC or Panel
Circuit Output
Point
Local Mode
Group Point
Types
Device Function
CONTROL
Y
N
Y
NAC
n/a
Supervised NAC
RELAY
Y
N
Y
Relay
n/a
Relay output
BELL CIRCUIT
Y
N
Y
NAC
fire
Supervised NAC
STROBE CKT
Y
N
Y
NAC
fire
Supervised NAC
HORN CIRCUIT
Y
N
Y
NAC
fire
Supervised NAC
AUDIBLE CKT
Y
N
Y
NAC
fire
Supervised NAC
SPEAKER
Y
N
Y
NAC
fire
Supervised NAC for speaker circuits
blank
Y
N
Y
NAC
n/a
Supervised NAC for undefined device
NONRESET
CTL
N
N
N
Relay or NAC
n/a
Supervised output, unaffected by “System Reset”
command
TELEPHONE
N
N
N
Relay
fire
Supervised Telephone circuit
CONTROL NAC
Y
N
Y
NAC
fire
Supervised NAC
ISOLATED NAC
Y
N
Y
NAC
fire
Supervised NAC for notification appliance, used
with audio isolators. Activates even if there is a
short on its NAC circuit. For ULC installations only.
ISOLATED SPK
Y
N
Y
NAC
fire
Supervised NAC for speaker circuits, used with
audio isolators. Activates even if there is a short on
its audio circuit. For ULC installations only.
GEN ALARM
N
Y
Y
NAC
fire
Control Module, XPC-8, or an XP5-C (in NAC
mode) configured as a Municpal Box Transmitter for
NFPA 72 Auxiliary Fire Alarm Systems applications
(MBT-1 required). This Type ID can also be used for
general alarm activation.
GEN SUPERVIS
N
Y
Y
NAC
supervisory Control Module, XPC-8, or an XP5-C (in NAC mode)
activated under any Supervisory condition (includes
sprinkler type).
GEN TROUBLE
N
Y
Y
NAC
trouble
Control Module, XPC-8, or an XP5-C (in NAC mode)
activated under any System Trouble condition.This
device will not turn ON when it is in trouble (short or
open).
GENERAL
PEND
N
Y
Y
NAC
trouble
Control Module XPC-8 circuit, or an XP5-C (in NAC
mode) that will activate upon receipt of an alarm
and/or trouble condition, and remain in the ON state
until all events have been ACKNOWLEDGED. This
device will not turn ON when it is in trouble (short or
open)
TROUBLE
PEND
N
Y
Y
NAC
trouble
Control Module or an XP5-C (in NAC mode) that will
activate upon receipt of a trouble condition, and
remain in the ON state until all troubles have been
ACKNOWLEDGED. This device will not turn ON
when it is in trouble (short or open).
ALARMS PEND
N
Y
Y
NAC
fire
Control module/panel circuit or NAC for output that
will activate upon receipt of an alarm condition, and
remain in the alarm state until all alarms have been
acknowledged.
INST RELEASE
N
Y
N
NAC (SLC only)
fire
Supervised for open circuits and ground faults.
Short = normal
REL. FORM C
N
Y
N
Form-C relay
(SLC only)
n/a
Directs relay outputs to perform a releasing function.
RELEASE CKT
N
Y
N
NAC (SLC only)
n/a
Directs outputs to perform a releasing function.
REL CKT ULC
N
Y
N
NAC (SLC only)
n/a
Directs outputs to perform a release function as
required by ULC.
REL END BELL
N
Y
N
NAC
n/a
Activates NAC audio or visual device when
releasing circuits shut off.
REL AUDIBLE
Y
Y
N
NAC
n/a
Activates audio or visual devices steady when
releasing starts.
FORM C
RESET
N
Y
N
Form-C Relay
(SLC only)
n/a
Control module used to interrupt 24V power to four-
wire conventional detectors for 30 seconds upon
reset. Used in conjunction with a monitor module
with a conventional detector Type ID
*
Values represent program defaults
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...