42
IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
Program
Point Program
•
for heat detectors, the settings are to degrees Centigrade.
•
for beam detectors, there are only six levels of Alarm. There is no Prealarm for beam detectors
in CLIP mode.
Alarm sensitivity settings range from one to nine, with one representing the most sensitive alarm
level and nine the least sensitive.
Prealarm sensitivity settings range from zero to nine. Zero indicates no prealarm. A value of one
can be a self-optimizing setting where the control panel selects a suitable prealarm level for the
detector. Values one or two through nine represent decreasing sensitivity, with nine being the least
sensitive.
Refer to the section “Detector Sensitivity Settings” in Appendix D, “AWACS™ Applications” for a
full description and a table of the nine sensitivity levels by detector type.
Soft Keys
OCCUPIED SENSITIVITY ALARM
:
OCCUPIED SENSITIVITY PREALARM
:
UNOCCUPIED SENSITIVITY ALARM:
UNOCCUPIED SENSITIVITY PREALARM:
ALARM SENSITIVITY TABLE:
This table will toggle from
ALARM
to
PREALARM
based on
which sensitivity value is being entered. The table will display the values for this type of detector.
Detector Occupancy Schedule
Figure 3.29 Detector Occupancy Schedule Screen
Soft Keys
WEEKLY OCCUPANCY SCHEDULE:
Press this soft key to place the cursor at the underlined
field. There can be up to ten Weekly Occupancy Schedules. Enter a value of zero through ten. Zero
indicates no schedule is applied, and occupied detector sensitivity values are used.
ACCEPT:
Press this key to accept the change made and return to the previous screen.
Press the soft key next to
these setting categories to
enter values as described
above.
D E T E C T O R O C C U P A N C Y S C H E D U L E
W E E K L Y O C C U P A N C Y S C H E D U L E : 1 0
S U N D A Y
-
-
M O N D A Y
0 8 : 0 0 - 1 2 : 0 0 , 1 3 : 0 0 - 1 8 : 0 0
T U E S D A Y
0 8 : 0 0 - 1 2 : 0 0 , 1 3 : 0 0 - 1 8 : 0 0
W E D N E S D A Y
0 8 : 0 0 - 1 2 : 0 0 , 1 3 : 0 0 - 1 8 : 0 0
T H U R S D A Y
0 8 : 0 0 - 1 2 : 0 0 , 1 3 : 0 0 - 1 8 : 0 0
F R I D A Y
0 8 : 0 0 - 1 2 : 0 0 , 1 3 : 0 0 - 1 8 : 0 0
S A T U R D A Y
0 8 : 0 0 - 1 2 : 0 0 ,
-
H O L I D A Y
U N O C C U P I E D
A C C E P T
B A C K
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...