IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
129
Equations
CBE: Zones and Equations
OR(AND(L1D1,L1D4),AND(L2D6,L2M3,NOT(L2M4)),ANY2(L1M13,L1M14,L1M15))
E.2.3 Trouble Equations
A trouble equation follows the same syntax rules as the logic equation. The system allows up to a
hundred trouble equations, ZT001 through ZT100. It differs from a logic equation in the following
manner:
•
Equations evaluate as true when the arguments go into trouble.
•
Argument entries may consist of system trouble codes. Refer to Appendix H, “System
Troubles” for a listing of these codes.
Examples:
AND(L1M149,L2M110) will evaluate as true when both arguments go into trouble.
OR(ZT049,ZT050) will evaluate as true when either argument goes into trouble.
These
have to be
ON
These have
to be ON.......and this OFF
Any TWO of
these have to be
ON
for this part to be TRUE
for this part to be TRUE
for this part to be TRUE
When this is TRUE
OR
When this is TRUE
OR
When this is TRUE
Then all outputs programmed with this equation will be turned ON.
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...