IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
93
Abort Switches
Releasing Applications
B.3.2 IRI Abort Switch
An IRI Abort Switch has a standard UL-type delay timer that complies with UL Standard 864,
operating like ULI but with additional functions for Cross Zones. Refer to “How Cross Zones
Work” on page 98 in this appendix for more information on cross zones.
When the first alarm occurs in a releasing zone programmed with a cross-zone code, pressing the
abort switch will prevent activation of the releasing zone should a second alarm occur while the
switch is held.
When the abort switch is released, if a second alarm has occurred while the switch was held, the
ten-second IRI timer activates immediately, and the control panel activates the releasing zone
outputs at the end of the IRI timer countdown.
When the abort switch is released and a second alarm has not occurred while the switch was held,
the panel waits for the cross-zone conditions to be met before activating the releasing zone.
Figure B.4 IRI Abort Switch
!
WARNING:
The IRI abort switch will only work if it is pushed before the second alarm occurs. If it is pushed after
the second alarm, the releasing zone will already have been activated, and the switch will have no
effect.
Delay Time: 15 seconds
Abort Switch: IRI
Cross Zone: Z
Soak Time: 0
Program selections for this releasing zone
Release the abort
switch; a 10-second
IRI timer begins
Abort Switch held 15 sec.
Press and hold
the Abort
Switch for 15
seconds
10 sec.
At the end of the 10
seconds, the
control panel
activates releasing
zone outputs
10 sec
Alarm 1
5 sec.
0 sec.
5 sec.
10 sec.
20 sec.
30 sec.
Alarm 2
(Cross-zone
conditions met)
5 sec.
Total time from when Abort Switch is
pressed to output activation: 15 + 10 =
25 seconds
Total time from when Abort Switch is
released to output activation: 10
seconds
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...