106
IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
Releasing Applications
Abort Switches
How to Program a ULC Release Circuit
The following contains information needed to program a ULC Release Circuit for an SLC output
module
.
NOTE:
A ULC Release Circuit with this Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit ; Non-Silenceable; No
Walk Test.
Description
An SLC output module used to activate a releasing solenoid or other releasing device. Multiple
outputs with the
REL
CKT
ULC
Type Code can also be mapped to the same Releasing Zone. When
the Releasing Zone activates, all outputs with the
REL
CKT
ULC
Type Code also activate at the
same time. A ULC Release Circuit activates when:
• An initiating device programmed to the same Releasing Zone activates (two devices if
using the Cross Zone option)
• The Delay Timer for the Releasing Zone (if used) expires
• No Abort Switch for the Releasing Zone (if used) is active
A ULC Release Circuit —and all wiring to the release device—is fully supervised and usable with
power-limited energy cable.
Program
Select an SLC output module to use for a ULC Release Circuit. While programming the point
(refer to the Point Programming section of this manual for instructions),
1.
Select the
REL
CKT
ULC
Type Code,
2.
Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).
Example
A programming example of a control module programmed as a ULC Release Circuit for Releasing Zone ZR05.
Figure B.14 Output Module Configured as a ULC Release Circuit
Type Code
REL
CKT
ULC
ZR05
Monitor
Module
Detector
Detector
Detector
Type Code
REL
CKT
ULC
SLC
output
module
SLC
output
module
A
SLC
output
module
B
SLC
output
module
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...