Appendix F: Detector Initialization
F.1 Overview
The control panel automatically performs a detector initialization routine when a detector is added
or changed.
The detector initialization routine takes approximately 2.5 minutes. During this time, the detector
being initialized does not perform fire protection functions. The LEDs of detectors polled in
FlashScan mode will latch a steady green while initializing, and return to blinking green when
initialization is over.
While initializing a detector, follow these guidelines:
• Make sure the detector is free of residual smoke during detector initialization.
• Do not test a detector during detector initialization.
WARNING:
If any detector is replaced with a different type of detector (for example, a laser detector is replaced
with a photoelectric detector), the control panel must be programmed immediately with the new
detector Type Code. Failure to do so can cause incorrect control panel operation, including false
alarms.
F.2 To Replace a Detector with a Different Type of Detector
If one type of detector is replaced with a different type of detector, the control panel must
immediately be programmed for the new detector type. To replace a detector, follow these steps:
NOTE:
The control panel only performs detector initialization if it senses that a detector was
removed for at least 15 seconds.
Step
Action
1
Delete the old detector point from FACP programming using the “Delete Point” screen on
page page 57.
2
Physically remove the old detector.
3
Enter point programming for this point and change the Type and FlashScan Code Label to
the values appropriate for the new detector. (Refer to “Detector Point” on page 38 for
programming instructions).
4
Physically install the new detector. Initialization will occur automatically
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...