IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
95
Abort Switches
Releasing Applications
expire at 150 seconds: however, this time exceeds the maximum of 120 seconds, so the releasing
zone outputs will begin releasing at 120 seconds, not at 150. Following is a graphic example of an
NYC Abort Switch and a delay timer programmed to a releasing zone.
Figure B.6 NYC Abort Switch -Example 2
Delay Time: 60 seconds
Abort Switch: NYC
Cross Zone: N
Soak Time: 0
Program selections for this releasing zone
Delay Time=60 sec.
Press and hold
the Abort Switch
The control panel activates
releasing zone outputs
after 120 seconds have
elapsed. The NYC timer
has not expired, but it is
overridden by the control
panel.
30 sec.
10 sec.
120 sec. to release
Total time from alarm initiation to release:
10 + 30 + 60 + 60 = 160 seconds
Alarm
0 sec.
NYC Delay=90 sec.
Release Abort Switch---
At this point, the delay becomes
the programmed Delay Time (60
seconds) plus the NYC Delay (90
seconds), which is 150 seconds,
OR 120 seconds, whichever is
smaller.
Pressing and releasing abort switch
restarts Delay Time=60 countdown after
40 seconds have elapsed.
Delay=60 sec.
150 sec. (60 + 90).
Exceeds 120 seconds
.
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...