24
IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
Program
Panel Program
Figure 3.8 Panel Timers (Menu 1) Screen
Soft Keys
VERIFY
TIME:
Press this soft key to set the Alarm Verification timer. Type in a value of 0-60
(seconds), which will delay initiating devices set for Alarm Verification from signaling for the
amount of time entered. If a second alarm occurs while the alarm verification timer is counting, the
timer will stop and the alarm will signal immediately. Default:
30
NOTE:
This value may not exceed 30 seconds for ULC installations.
MAXIMUM VERIFICATION COUNT:
Press and enter a value from 0-20 for a maximum
verification count threshold value that applies to detectors set to participate in Alarm Verification.
A value of zero produces no verification trouble. When the counter exceeds the threshold value
entered, a trouble is generated to the panel. Default:
20
AC
FAIL
DELAY:
Press this soft key to set the timing for the time delay from AC Failure to when
the trouble is reported. Type in a value of 6-12 (hours), or 0 (zero). A value of zero will cause
immediate notification. Default:
8
The onboard trouble relay ( TB3 on the CPU-3030 ) will activate and TM-4s will report according
to this setting.
UDACTs are notified immediately of AC failure by the panel, regardless of the panel’s delay
setting. Once the UDACT receives notification, it operates according to its own programmed AC
Fail Delay reporting schedule.
Example: AC Failure occurs at 1:00 p.m. on a panel with an AC FAIL DELAY setting of 8
hours. The UDACT is set for notification after 6 hours.
The AMPS-24, ACPS-2406, and XPIQ power supplies must be set to an AC Delay value of 0
(zero) when used with this panel.
SILENCE
INHIBIT:
Press to enter a value from 0 (disabled) to 5 minutes. This software timer
disables the SIGNAL SILENCE key function for the time entered when a fire alarm occurs. The
timer starts at the first alarm only; it does not restart with each new alarm. Default:
0
Time
Event
1:00 p.m.
AC Failure. Panel notifies UDACT. Panel and UDACT timers begin countdown to
report time.
7:00 p.m.
UDACT reports.
9:00 p.m.
TM-4 reports, TB3 trouble relay activates.
P A N E L T I M E R S
V E R I F Y T I M E : 3 0
V E R I F Y = P R E A L A R M :
N O
M A X I M U M V E R I F I C A T I O N C O U N T : 0 0
A C F A I L D E L A Y :
8 H O U R S
M O R E
S I L E N C E I N H I B I T : 0 0 : 0 0
A C C E P T
A U T O S I L E N C E : O F F
B A C K
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...