Electrical installation
Page 100
8.10
Connector: CAN bus [X4]
8.10.1
Configuration on the device [X4]
D-SUB connector, 9-pin type, male
8.10.2
Mating connector [X4]
D-SUB connector, 9-pin type, female
Housing for a 9-pin D-SUB connector with locking screws of type 4/40 UNC
8.10.3
Pin assignment [X4]
Table 43:
Pin assignment CAN bus [X4]
Pin no.
Name
Value
Specification
1
Not used
6
GND
0 V
CAN-GND, electrically coupled to GND in the controller
2
CANL
*)
CAN low signal line
7
CANH
*)
CAN high signal line
3
GND
0 V
See pin no. 6
8
Not used
4
Not used
9
Not used
5
Shield
PE
Connector for the cable shield
*)
An external terminating resistor of 120
Ω
is required on both ends of the bus. If the bus ends are not formed by item Servo
Positioning Controller C 3-Series with integrated terminating resistors, we recommend using metal film resistors with a 1%
tolerance of type 0207, e.g. made by BCC, part no.: 232215621201.