Electrical installation
Page 102
The individual nodes of the network are always connected in line so that the CAN cable is looped through from controller
to controller (see
.
A terminating resistor of 120
Ω
±
5% must be present on both ends of the CAN bus cable. The item Servo Positioning
Controller C 3-Series is equipped with an integrated terminating resistor that can be activated/deactivated via the DIP
switch "CAN TERM" on the front panel (see
Shielded cables with exactly two twisted pairs must be used for cabling.
Use one twisted pair to connect CAN-H and CAN-L.
The cores of the other pair are used jointly for CAN-GND.
The shield of the cable is connected to the CAN shield connectors for all nodes.
For information about suitable and item-recommended cables, refer to
chapter 8.10.4, Cable type and configuration [X4]
We advise against the use of plug adaptors for cabling the CAN bus. However, if this is necessary, use metal connector
housings for connecting the cable shield.
In order to keep interferences as low as possible ensure that
the motor cables are not installed parallel to signal lines
the motor cables comply with the item specification
the motor cables are properly shielded and earthed (grounded)
For further information on interference-free CAN bus cabling, please refer to the Controller Area Network protocol
specification, version 2.0, by Robert Bosch GmbH, 1991.
integrated
terminating resistor
120
Ω
X4, Pin 7
(CAN-H)
X4, Pin 2
(CAN-L)
DIP switch
CAN TERM
Figure 26:
Integrated CAN terminating resistor